Operating instructions

G3G146-AB54-01

Translation of the original operating instructions

4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing the blower
from the packaging

→ Carefully remove the blower from its packaging, only

touching the housing. Make sure to avoid any shock.

→ Wear safety shoes and cut-resistant safety gloves.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Install the undamaged device according to your application.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

DANGER
Electrical load (>50 µC) between mains wire and
protective earth connection after switching of the supply
when switching multiple devices in parallel.

Electric shock, risk of injury
→ Make sure that sufficient protection against accidental contact

is provided.
Before working on the electrical connection, the
connections to the mains supply and PE must be shorted.

CAUTION
Electrical voltage

The device is a built-in component and features no electrically
isolating switch.
→ Connect the device only to circuits that can be switched off

using an all-pole disconnecting switch.

→ When working on the device, you must switch off the

system/machine in which the device is installed and secure
it from being switched on again.

NOTE
Interferences and failures are possible

Maintain a distance to the power supply line when routing the
control lines of the device.
→ Ensure a sufficiently large clearance.

Recommendation: clearance > 10 cm (separate cable
routing)

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.

→ Make sure that the cable end is connected in a dry

environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

;

Check whether the data on the type plate agree with the connection
data.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

4.2.2 Idle current

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.

4.2.3 Locked-rotor protection

Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connection of the cables

External leads are brought out of device.

;

First connect the "PE" (protective earth) connection.

;

Connect the lines according to your application. When doing so,
observe chapter 4.4 Connection screen.

Item no. 50962-5-9970 · Revision 72864 · Release 2011-02-18 · Page 6 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание G3G146-AB54-01

Страница 1: ...ised specialist personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards...

Страница 2: ...ire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against accidental contact Befo...

Страница 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Страница 4: ...sures have the unit mm 1 Connection line AWG18 3 x crimped core end sleeves 2 Control line AWG22 4 x crimped core end sleeves Item no 50962 5 9970 Revision 72864 Release 2011 02 18 Page 4 10 ebm papst...

Страница 5: ...0 measuring network Fig 4 TN system 3 5 mA Motor protection Thermal overload protector TOP wired internally Cable exit Variable Protection class I if protective earth is connected by customer Product...

Страница 6: ...es are possible Maintain a distance to the power supply line when routing the control lines of the device Ensure a sufficiently large clearance Recommendation clearance 10 cm separate cable routing NO...

Страница 7: ...8 0 10 V PWM yellow Control input 0 10 V or PWM electrically isolated 9 Tach white Tach output open collector 1 pulse per revolution electrically isolated 11 10V max 1 1 mA red Voltage output 10 V ma...

Страница 8: ...he device by changing the input signal 4 7 Switching off the device Switching off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation...

Страница 9: ...tector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device...

Страница 10: ...eplace wires Check the ball bearings to ensure they are quiet can move easily and are free of play Manual check by turning the rotor in shut off state At least every 6 months Replace device in case of...