background image

Operating instructions

G2E140-AG02-78

Translation of the original operating instructions

3.2 Nominal data

Motor

M2E068-DF

Phase

1~

Nominal voltage / VAC

230

Frequency / Hz

50

Type of data definition

ml

Valid for approval /
standard

CE

Speed / min

-1

2000

Power input / W

200

Current draw / A

0.88

Motor capacitor / µF

4

Capacitor voltage / VDB

400

Capacitor standard

P2 (CE)

Min. back pressure / Pa

100

Min. ambient temperature
/ °C

-

Max. ambient
temperature
/ °C

50

Starting current / A

1.2

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Technical features

Mass

3.5 kg

Size

140 mm

Surface of rotor

Coated in black

Material of protective
cover

Sheet steel, thick-film-passivated

Material of impeller

Aluminium sheet, coated in black

Housing material

Die-cast aluminium, coated in black

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP 20

Insulation class

"F"

Humidity class

F0

Mounting position

Any

Condensate discharge
holes

None, open rotor

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

< 0.75 mA

Electrical leads

Via terminals, capacitor connected via
terminals

Motor protection

Thermal overload protector (TOP) wired
internally

Protection class

I (if protective earth is connected by
customer at the connection point of the
housing)

Product conforming
to standard

EN 60335-1; CE

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.4 Mounting data

For depth of screw, see chapter 3.1 Product drawing

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.5 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+ 80 °C

Min. permissible
ambient motor temp.
(transp./storage)

- 40 °C

Item no. 13679-5-9970 · Revision 81525 · Release 2014-06-02 · Page 5 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание G2E140-AG02-78

Страница 1: ...ed trained and authorised technical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety ru...

Страница 2: ...ewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or jewellery while working on rotating parts Protect long hair by wearing a cap 1 7 Emiss...

Страница 3: ...the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highl...

Страница 4: ...drawing All measures have the unit mm 1 brown capacitor 2 N black capacitor 3 L blue 4 Flat plug 6 3 x 0 8 PE Item no 13679 5 9970 Revision 81525 Release 2014 06 02 Page 4 9 ebm papst Mulfingen GmbH...

Страница 5: ...ng Ball bearing Touch current acc IEC 60990 measuring network Fig 4 TN system 0 75 mA Electrical leads Via terminals capacitor connected via terminals Motor protection Thermal overload protector TOP w...

Страница 6: ...ting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current according to the type plate For determining the cross section follow the...

Страница 7: ...operating instructions 4 4 Connection screen L blue N black Item no 13679 5 9970 Revision 81525 Release 2014 06 02 Page 7 9 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938...

Страница 8: ...cting the voltage at all poles before opening the device CAUTION Electrical load on the capacitor after device is switched off Electric shock risk of injury Discharge the capacitors before working on...

Страница 9: ...to clean 5 2 Safety test What has to be tested How to test Frequency Which measure Check the protective casing against accidental contact for damage and to ensure that it is intact Visual inspection...

Отзывы: