Operating instructions

G2D160-AF02-34

Translation of the original operating instructions

4.2.3 Variable frequency drive

Please use a variable frequency drive only after consultation with ebm-
papst.

For operation with variable frequency drives, install sinusoidal
filters that work on all poles (phase-phase and phase-ground)
between the drive and the motor.
During operation with variable frequency drives, an all-pole
sine filter protects the motor against high-voltage transients that
can destroy the coil insulation system, and against harmful
bearing currents.

Heating-up of the motor when using a variable frequency drive must be
checked by the customer following installation in the end device.

4.3 Connection in terminal box

4.3.1 Preparing cables for connection

Only strip the cable as far as necessary, ensuring that the cable gland is
sealed and there is no strain on the connections. For tightening torques,
see Chapter 3.1 Product drawing.

NOTE
Tightness and strain relief are dependent on the cable
used.

→ This must be checked by the user.

4.3.2 Connecting wires to terminals

;

Remove the cap from the cable gland.

Only remove caps where cables are fed in.

;

Route the wire(s) (not included in scope of delivery) into the terminal
box.

;

Connect the wires to the corresponding terminals.

Use a screwdriver to do so.
When connecting, ensure that no wire ends fan out.

;

Seal the terminal box.

4.3.3 Cable routing

Water must be prevented from reaching the cable gland along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.

Fig. 2: Cable routing for fans installed upright.

4.3.4 Motor protection

WARNING
Device has no overheating protection

The device is supplied without any automatic overheating
protection. The device can become hot and catch fire.
→ For the version without thermal overload protector, also

install a suitable motor protection switch.

Item no. 14834-5-9970 · ENU · Change 213208 · Approved 2020-07-14 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание G2D160-AF02-34

Страница 1: ...qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic sa...

Страница 2: ...e Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or dangling clothing or jewelry whi...

Страница 3: ...be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fa...

Страница 4: ...1 Tightening torque 1 3 0 2 Nm 2 Cable diameter min 6 mm max 8 mm tightening torque 2 0 3 Nm 3 M4 screw for fastening ground connector Item no 14834 5 9970 ENU Change 213208 Approved 2020 07 14 Page...

Страница 5: ...minum Impeller material Sheet steel painted black Housing material Die cast aluminum Direction of rotation Clockwise viewed toward rotor Degree of protection IP44 installation and position dependent a...

Страница 6: ...e disconnection switch When working on the device secure the system machine in which the device is installed so as to prevent it from being switched back on NOTE Water ingress into wires or cables Wat...

Страница 7: ...the wire s not included in scope of delivery into the terminal box Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no wire ends fan out Seal th...

Страница 8: ...ion by reversing two phases Y Star connection Delta connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white Item no 14834 5 9970 ENU Change 213208 Approved 2020 07 14 Page 8 11 ebm p...

Страница 9: ...tching off the device Disconnect the device from the power supply at the supply line s main switch 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Sen...

Страница 10: ...ing noise acoustic At least every 6 months Replace device 5 3 Disposal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operates an environme...

Страница 11: ...pose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 14834 5 9970 ENU Change 213208 Approved 2020 07...