4. CONNECTION AND START-UP

4.1 Connecting the mechanical system

CAUTION
Cutting and crushing hazard when removing the blower
from the packaging

→ Carefully remove the blower from its packaging, only

touching the housing. Make sure to avoid any shock.

→ Wear safety shoes and cut-resistant safety gloves.

;

Check the device for transport damage. Damaged devices must no
longer be installed.

;

Install the undamaged device according to your application.

4.2 Connecting the electrical system

DANGER
Electric voltage on the device

Electric shock
→ Always install a protective earth first.
→ Check the protective earth.

DANGER
Incorrect insulation

Risk of fatal injury from electric shock
→ Use only cables that meet the specified installation

requirements for voltage, current, insulation material, load etc.

→ Route cables such that they cannot be touched by any

rotating parts.

CAUTION
Electrical voltage

The device is a built-in component and features no electrically
isolating switch.
→ Connect the device only to circuits that can be switched off

using an all-pole disconnecting switch.

→ When working on the device, you must switch off the

system/machine in which the device is installed and secure
it from being switched on again.

NOTE
Interferences and failures are possible

Maintain a distance to the power supply line when routing the
control lines of the device.
→ Ensure a sufficiently large clearance.

Recommendation: clearance > 10 cm (separate cable
routing)

NOTE
Water penetration into leads or wires

Water enters at the cable end on the customers side and can
damage the device.
→ Make sure that the cable end is connected in a dry

environment.

Connect the device only to circuits that can be switched off
using an all-pole disconnecting switch.

4.2.1 Prerequisites

;

Check whether the data on the type plate agree with the connection
data.

;

Before connecting the device, ensure that the supply voltage matches
the operating voltage of the device.

;

Only use cables designed for current according to the type plate.
For determining the cross-section, follow the basic principles in
accordance with EN 61800-5-1. The protective earth must have a
cross-section equal to or greater than the outer conductor cross-
section.
We recommend the use of 105°C cables. Ensure that the minimum
cable cross-section is at least
AWG26/0.13 mm².

Earth wire contact resistance in accordance with EN 60335

Compliance with the impedance specifications in accordance with EN
60335 for the protective earth circuit must be verified in the end
application.
Depending on the installation situation, it may be necessary to install an
additional protective earthing conductor via the additional protective earth
connection point available on the device.

4.2.2 Idle current

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and interference immunity), idle
currents in the mains cable can be measured even when the
motor is at a standstill and the mains voltage is switched on.

4.2.3 Locked-rotor protection

Due to the locked-rotor protection, the start-up current (LRA) is
equal to or less than the nominal current (FLA).

Item no. 50989-5-9970 · Revision 72138 · Release 2014-01-24 · Page 6 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

E-mail: [email protected]  

Содержание G1G140-AW31-42

Страница 1: ...chnical staff Only authorised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules...

Страница 2: ...come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING R...

Страница 3: ...ructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Moving air that contains abrasive particles Moving highly corrosive air e g salt spray mis...

Страница 4: ...3 TECHNICAL DATA 3 1 Product drawing All measures have the unit mm 1 Shown without cover Item no 50989 5 9970 Revision 72138 Release 2014 01 24 Page 4 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D...

Страница 5: ...Variable Protection class I if protective earth is connected by customer Product conforming to standard EN 60335 1 Approval VDE For cyclic speed loads note that the rotating parts of the device are d...

Страница 6: ...e end on the customers side and can damage the device Make sure that the cable end is connected in a dry environment Connect the device only to circuits that can be switched off using an all pole disc...

Страница 7: ...e original operating instructions 4 3 Connection screen Item no 50989 5 9970 Revision 72138 Release 2014 01 24 Page 7 10 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938 81...

Страница 8: ...Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 6 Switching off the device Switching off the device during operation Switch off the device via the contr...

Страница 9: ...nergise correct connection see connection diagram Overtemperature of electronics motor Insufficient cooling Improve cooling Let the device cool down To reset the error message switch off the mains sup...

Страница 10: ...the insulation of the wires for damage Visual inspection At least every 6 months Replace wires Item no 50989 5 9970 Revision 72138 Release 2014 01 24 Page 10 10 ebm papst Mulfingen GmbH Co KG Bachm hl...

Отзывы: