Operating instructions

D4D225-GH02-01

Translation of the original operating instructions

Heating-up of the motor when using voltage control must be checked by
the customer following installation in the end device.

4.2.4 Frequency inverter

Please use a frequency converter only after consultation with ebm-papst.

For operation with frequency converters, fit sinusoidal filters that
work on all poles (phase-phase and phase-earth) between the
frequency converter and the motor.
During operation with frequency converters, an all-pole sine
filter protects the motor against high-voltage transients that can
destroy the winding insulation system, and against harmful
bearing currents.

Heating-up of the motor when using a frequency converter must be
checked by the customer following installation in the end device.

4.3 Connection of the cables

External leads are brought out of device.

;

First connect the "PE" (protective earth) connection.

Connect the lines according to your application. When doing so,
observe chapter 4.4 Connection screen.

4.3.1 Motor protection

CAUTION
Voltage

The device is a built-in component with no isolating switch.
→ Connect the device to a suitable tripping device.
→ Only connect the device to circuits which can be de-

energised with an all-pole disconnection switch.

→ When working on the device, the system/machine in

which the device is installed must be secured so as to
prevent it from being switched back on.

NOTE
Lack of motor protection

Without motor protection, the motor can overheat and suffer
damage.
→ Connect up the thermal overload protector installed in the coil.

The motors are equipped with thermal overload protectors to protect the
devices.
Check to make sure that the thermal overload protector is correctly
connected before each operation.
Failure to connect up the thermal overload protector correctly will
invalidate your warranty claim.

Item no. 12410-5-9970 · ENG · Revision 213948 · Release 2020-03-25 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание D4D225-GH02-01

Страница 1: ...horised specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards st...

Страница 2: ...stomer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the devic...

Страница 3: ...d and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted fr...

Страница 4: ...oduct drawing All measures have the unit mm 1 Connection line ETFE AWG18 6 x brass lead tips crimped Item no 12410 5 9970 ENG Revision 213948 Release 2020 03 25 Page 4 11 ebm papst Mulfingen GmbH Co K...

Страница 5: ...steel galvanised Housing material Sheet steel galvanised Motor suspension Motor mounted vibration free on both sides Direction of rotation Clockwise seen on rotor Type of protection IP20 Insulation c...

Страница 6: ...fficient protection against accidental contact is provided Before working on the electrical connection the connections to the mains supply and PE must be shorted CAUTION Electrical voltage The device...

Страница 7: ...e lines according to your application When doing so observe chapter 4 4 Connection screen 4 3 1 Motor protection CAUTION Voltage The device is a built in component with no isolating switch Connect the...

Страница 8: ...ion changes when two phases are reversed Y Star connection L1 U1 black L2 V1 blue L3 W1 brown PE green yellow TOP 2x grey Item no 12410 5 9970 ENG Revision 213948 Release 2020 03 25 Page 8 11 ebm paps...

Страница 9: ...irs on your device Return the device to ebm papst for repair or replacement WARNING Terminals and connections have voltage even with a unit that is shut off Electric shock Wait five minutes after disc...

Страница 10: ...Please contact ebm papst if bearing replacement is required after this period Adapt the maintenance intervals to the dust pollution occurring 5 2 Safety test What has to be tested How to test Frequen...

Страница 11: ...nium Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards On...

Отзывы: