ebm-papst D3G200-HD02-02 Скачать руководство пользователя страница 3

Operating instructions

D3G200-HD02-02

Translation of the original operating instructions

2. INTENDED USE

The device is exclusively designed as a built-in device for conveying
air according to its technical data.
Any other usage above and beyond this does not conform with the
intended purpose and constitutes misuse of the device.
Customer equipment must be capable of withstanding the mechanical
and thermal stresses that can arise from this product. This applies for the
entire service life of the equipment in which this product is installed.

Intended use also includes

The device is only to be used in power systems with grounded
neutral (TN/TT power systems), in power systems with phase
conductor grounding, or in IT power systems.

Use of the device in stationary systems only.

Performance of all maintenance work.

Conveying air at an ambient air pressure between 800 mbar and
1050 mbar.

Using the device within the permitted ambient temperature range; see
Chapter 3.6 Transport and storage conditions and
Chapter 3.2 Nominal data.

Operating the device with all protective devices.

Following the operating instructions.

Improper use

In particular, operating the device in the following ways is prohibited and
could be hazardous:

Operating the device in an unbalanced state, e.g. due to dirt deposits
or ice formation.

Resonant operation, operation with severe vibration. This also
includes vibration transmitted to the fan from the customer installation.

Operation in medical equipment with a life-sustaining or life-support
function.

Conveying solids in the flow medium.

Painting the device

Connections (e.g. screws) coming loose during operation.

Opening the terminal box during operation.

Conveying air that contains abrasive particles.

Conveying highly corrosive air, e.g. salt spray. Exception: devices
designed for salt spray and correspondingly protected.

Conveying air with high dust content, e.g. suctioning off sawdust.

Operating the device close to flammable materials or components.

Operating the device in an explosive atmosphere.

Using the device as a safety component or to perform safety-related
functions.

Operation with completely or partially disassembled or manipulated
protective devices.

In addition, all applications not listed among the intended uses.

Item no. 54389-5-9970 · ENU · Change 260673 · Approved 2022-06-23 · Page 3 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание D3G200-HD02-02

Страница 1: ... to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated with the device must be assessed again following installation in the final product The locally applicable industrial safety regulations are always to be observed when working on the device Keep the workplace clean and tidy U...

Страница 2: ...nt DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not w...

Страница 3: ...In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fan from the customer installation Operation in medical equipment with a life sustaining or life support function Conveyi...

Страница 4: ... GND 2 4 RSA 2 5 RSB 2 6 Tach 3 Tightening torque 3 0 5 Nm 4 Cable diameter min 6 mm max 10 mm tightening torque 1 8 0 3 Nm Cable diameter min 8 mm max 12 mm tightening torque 1 8 0 3 Nm use must be made of seal provided Item no 54389 5 9970 ENU Change 260673 Approved 2022 06 23 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 d...

Страница 5: ...s are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical description Weight 11 64 kg Size 200 mm Motor size 84 Rotor surface Painted black Impeller material Sheet ...

Страница 6: ...tly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Risk of physical injury such as back injuries Two people should work together to remove the device from its packaging NOTE Damage to the device from vibration Bearing damage shorter service life The fan must not be subjected to force or excessive vibration from sections of the installation I...

Страница 7: ...this operating state operational readiness is typically 4 W 4 2 3 Residual current circuit breaker RCCB If the use of a residual current device RCD is required in your installation only AC DC sensitive residual current devices type B or B are permissible As with variable frequency drives residual current devices cannot provide personal safety while operating the device When the device power supply...

Страница 8: ...e parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 1 Max PWM 100 Min PWM 10 Save set value to EEPROM No Set value requirement Analog linear Direction of action parameter set 1 Positive heating Direction of action parameter set 2 Positive heating Item no 54389 5 9970 ENU Change 260673 Approved 2022 06 23 Page 8 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mul...

Страница 9: ... contact common connection contact rating 250 VAC 2 A AC1 min 10 mA basic insulation on supply side and reinforced insulation on control interface side KL3 1 0 10 V Analog input set value 0 10 V Ri 100 kΩ adjustable curve SELV KL3 2 10 V Fixed voltage output 10 VDC SELV KL3 3 GND Reference ground for control interface SELV KL3 4 RSA RS485 interface for MODBUS RSA SELV KL3 5 RSB RS485 interface for...

Страница 10: ...remature failure 4 8 Switching off the device Switching off the device during operation Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the ...

Страница 11: ...nd rectify cause of error release restart lockout if necessary Ambient temperature too high Reduce the ambient temperature Reset by reducing control input to 0 Impermissible point of operation Correct the operating point Let the device cool down In the event of further malfunctions contact ebm papst 6 1 Cleaning To ensure a long service life check the fans regularly for proper operation and soilin...

Страница 12: ...requirements NOTE Country specific legal requirements Always observe the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also to be heeded 6 3 2 Disassembly Disassembly of the product must be performed or supervised by qualified personnel with the appropriate te...

Отзывы: