ebm-papst A6D910-AA01-01 Скачать руководство пользователя страница 5

Operating instructions

A6D910-AA01-01

Translation of the original operating instructions

3.2 Nominal data

Motor

M6D138-NA

Phase

3~

3~

Nominal voltage / VAC

400

400

Connection

Δ

Y

Frequency / Hz

50

50

Type of data definition

ml

ml

Valid for approval /
standard

CE

CE

Speed (rpm) / min

-1

885

685

Power input / W

2480

1570

Current draw / A

5.4

2.9

Max. back pressure / Pa

150

90

Min. ambient
temperature / °C

-40

-40

Max. ambient
temperature / °C

50

50

Starting current / A

18.6

6.2

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

37

36.1

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

40.9

40

05 Variable speed drive

No

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

A6D910-AA01-01

09 Power input P

e

/ kW

2.46

09 Air flow q

v

/ m³/h

22145

09 Pressure increase total p

fs

/

Pa

157

10 Speed (rpm) n / min

-1

900

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

27.8 kg

Size

910 mm

Motor size

138

Surface of rotor

Cast in aluminium

Material of terminal box

PP plastic

Material of blades

Aluminium sheet insert, sprayed with PP
plastic

Number of blades

5

Blade angle

Direction of air flow

V

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP54

Insulation class

"F"

Humidity (F) /
environmental
protection class (H)

H2

Note ambient
temperature

Occasional start-up between -40 °C and -
25 °C is permissible. For continuous
operation at ambient temperatures below -
25 °C (e.g. refrigeration applications), a
fan version with special low-temperature
bearings must be used.

Mounting position

Any

Condensation
drainage holes

On rotor and stator sides

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical connection

Terminal box

Motor protection

Thermal overload protector (TOP)
brought out, basic insulation

Cable exit

Axial

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60034-1 (2010); CE

Approval

VDE; EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

;

Use the device in accordance with its protection type.

Notes on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may vary during the production period.
Strength, dimensional stability and dimensional accuracy are not affected
by this.
The colour pigments of the paints used react perceptibly to UV light over
the course of time. To prevent the formation of patches and fading, the
product is to be protected against UV radiation. Changes in colour are
not a reason for complaint and are not covered by the warranty. UV
radiation in the frequency range and the intensity of natural solar radiation
has no effect on the technical properties of the products.

Item no. 10756-5-9970 · ENG · Revision 232542 · Release 2021-06-22 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A6D910-AA01-01

Страница 1: ... specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the end device The local industrial safety regulations must always be observed when working on the device Keep the workplace clean and tidy...

Страница 2: ...m machine wait until all parts have come to a standstill WARNING Rotating device Long hair dangling items of clothing jewellery and similar items can become entangled and be pulled into the device Risk of injury Do not wear any loose fitting or dangling clothing or jewellery while working on rotating parts Protect long hair with a cap 1 7 Emission WARNING Depending on the installation and operatin...

Страница 3: ...cularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system to the fan Operation in medical equipment with a life sustaining or lifesaving function Moving solids content in flow medium Painting the device Connections e g...

Страница 4: ... 1 Direction of air flow V 2 Thread reach max 18 mm 3 Tightening torque 1 5 0 2 Nm 4 Cable diameter min 7 mm max 14 mm tightening torque 2 0 3 Nm Item no 10756 5 9970 ENG Revision 232542 Release 2021 06 22 Page 4 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 5: ... blades Aluminium sheet insert sprayed with PP plastic Number of blades 5 Blade angle 0 Direction of air flow V Direction of rotation Clockwise seen on rotor Type of protection IP54 Insulation class F Humidity F environmental protection class H H2 Note ambient temperature Occasional start up between 40 C and 25 C is permissible For continuous operation at ambient temperatures below 25 C e g refrig...

Страница 6: ...application Do not make any modifications additions or renovations to the device Replacing the terminal box is not permitted CAUTION Possibility of damage to the device Serious damage may result if the device slips during assembly Keep the device fixed in position at the installation location until all attachment screws have been tightened The fan must not be strained on fastening 4 2 Connecting t...

Страница 7: ...estroy the winding insulation system and against harmful bearing currents Heating up of the motor when using a frequency converter must be checked by the customer following installation in the end device 4 3 Connection in terminal box 4 3 1 Preparing connection lines for the connection Strip the cable just enough so that the screwed cable gland is tight and the terminals are relieved of strain Tig...

Страница 8: ...t from being switched back on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect up the thermal overload protector installed in the coil The motors are equipped with thermal overload protectors to protect the devices Check to make sure that the thermal overload protector is correctly connected before each operation Failure to connect up the ther...

Страница 9: ...tion Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 10756 5 9970 ENG Revision 232542 Release 2021 06 22 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachmühle 2 D 74673 Mulfingen Phone 49 0 7938 81 0 Fax 49 0 7938 81 110 info1 de ebmpapst com www ebmpapst com ...

Страница 10: ...trong vibrations can result from improper handling imbalance resulting from damage during transport or component induced or structural resonances When putting the fan into service determine the speed ranges with excessive vibration levels and also any resonance frequencies that may be present When regulating the speed pass through resonance ranges as quickly as possible or find another remedy Oper...

Страница 11: ...t basedcleaning agents Do not use any pointed or sharp edged objects for cleaning Completely remove any cleaning agents used Immediately switch off and replace the device if severe corrosion is apparent at load bearing or rotating parts Repairs to load bearing or rotating parts are not permissible Operate the fan for 2 hours at maximum speed to permit the evaporation of any water which may have in...

Страница 12: ...nts could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 5 3 3 Component disposal The products are mostly made of steel copper aluminium and plastic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron...

Отзывы: