3.2 Nominal data

Motor

M4D110-IA

Phase

3~

3~

3~

3~

Nominal voltage / VAC

230

230

277

400

Wiring

Δ

Δ

Δ

Y

Frequency / Hz

50

60

60

50

Method of obtaining
data

ml

ml

ml

ml

Valid for approval/
standard

CE

CE

CE

CE

Speed (rpm) / min

-1

1390

1575

1640

1390

Power consumption / W

880

1320

1420

880

Current draw / A

3.72

4.26

4.39

2.15

Max. back pressure / Pa

170

215

230

170

Min. ambient
temperature / °C

-40

-40

-40

-40

Max. ambient
temperature / °C

65

65

65

65

Starting current / A

17

15

19

10

Phase

3~

3~

Nominal voltage / VAC

400

480

Wiring

Y

Y

Frequency / Hz

60

60

Method of obtaining
data

ml

ml

Valid for approval/
standard

CE

CE

Speed (rpm) / min

-1

1575

1640

Power consumption / W

1320

1420

Current draw / A

2.46

2.54

Max. back pressure / Pa

215

230

Min. ambient
temperature / °C

-40

-40

Max. ambient
temperature / °C

65

65

Starting current / A

8.9

11.2

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

36.1

33.3

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

42.8

40

05 Variable speed drive

No

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

A4D560-AR03-03

09 Power consumption P

e

/ kW

0.87

09 Air flow q

v

/ m³/h

6755

09 Pressure increase total p

sf

/

Pa

169

10 Speed (rpm) n / min

-1

1390

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

12.1 kg

Size

560 mm

Motor size

110

Rotor surface

Cast in aluminum

Terminal box material

PP plastic

Blade material

Sheet aluminum insert, sprayed with PP
plastic

Number of blades

5

Blade pitch

-10°

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H2

Ambient temperature
note

Occasional start-up at temperatures
between -40°C and -25°C is permitted.
For continuous operation at ambient
temperatures below -25°C (such as
refrigeration applications), use must be
made of a fan design with special low-
temperature bearings.

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Thermal overload protector (TOP) with
basic insulation

with cable

Axial

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

Item no. 10611-5-9970 · ENU · Change 98149 · Approved 2021-01-26 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A4D560-AR03-03

Страница 1: ...authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic...

Страница 2: ...the system machine wait until all parts have come to a standstill WARNING Rotating device Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the dev...

Страница 3: ...following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also i...

Страница 4: ...flow direction V 2 Max clearance for screw 12 mm 3 Tightening torque 1 5 0 2 Nm 4 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 10611 5 9970 ENU Change 98149 Approved 2021 01 26...

Страница 5: ...isposal is provided in the operating instructions 13 Maintenance Information on installation operation and maintenance is provided in the operating instructions 14 Additional components Components use...

Страница 6: ...blades near the hub Strictly avoid shocks Wear safety shoes and cut resistant safety gloves CAUTION Heavy load when unpacking device Risk of physical injury such as back injuries Two people should wo...

Страница 7: ...on situation it may be necessary to connect an additional protective earth conductor by way of the extra protective earth terminal provided on the device The protective earth terminal is located on th...

Страница 8: ...talled lying flat cable routed in a U shaped loop Fans installed upright When routing the cable make sure that the cable glands are located at the bottom The cables must always be routed downward Fig...

Страница 9: ...tion Y Star connection L1 V1 blue L2 U1 black L3 W1 brown W2 yellow U2 green V2 white TOP 2x gray PE green yellow Item no 10611 5 9970 ENU Change 98149 Approved 2021 01 26 Page 9 12 ebm papst Mulfinge...

Страница 10: ...inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant frequencies...

Страница 11: ...nd replace it Repair of load bearing or rotating parts is not permitted Operate the fan for 2 hours at maximum speed so that any water that has ingressed can evaporate If cleaning does not eliminate v...

Страница 12: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...