ebm-papst A4D450-AU01-02 Скачать руководство пользователя страница 5

Operating instructions

A4D450-AU01-02

Translation of the original operating instructions

3.2 Nominal data

Motor

M4D094-EA

Phase

3~

3~

3~

3~

Nominal voltage / VAC

400

400

400

400

Connection

Δ

Y

Δ

Y

Frequency / Hz

50

50

60

60

Type of data definition

ml

ml

ml

ml

Valid for approval /
standard

CE

CE

CE

CE

Speed / min

-1

1250

875

1360

860

Power input / W

340

200

415

205

Current draw / A

0.61

0.33

0.70

0.35

Max. back pressure / Pa

120

60

85

35

Min. ambient temperature
/ °C

-40

-40

-40

-40

Max. ambient
temperature
/ °C

60

60

50

50

Starting current / A

1.7

0.55

1.57

0.51

Maximum safe operating
speed / min

-1

1850
@ 60 °C

1850
@ 60 °C

1850
@ 60 °C

1850
@ 60 °C

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

No

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

/ %

32

26.4

30.4

Efficiency grade N

41.6

36

40

Power input P

e

/ kW

0.3

Air flow q

v

/ m³/h

3610

Pressure increase total p

sf

/ Pa

96

Speed n / min

-1

1285

Data definition with optimum efficiency.

The ErP data is determined using a motor-impeller combination in a standardised

measurement configuration.

3.4 Technical features

Mass

4.7 kg

Size

450 mm

Surface of rotor

Coated in black

Material of terminal box

ABS plastic

Material of blades

Press-fitted sheet steel blank, sprayed
with PP plastic

Number of blades

5

Direction of air flow

"A"

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Thermal overload protector (TOP)
brought out

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 60034-1 (2010); CE

Approval

CCC; EAC

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

Item no. 11391-5-9970 · ENG · Revision 83823 · Release 2015-02-24 · Page 5 / 10

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A4D450-AU01-02

Страница 1: ...ecialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming fro...

Страница 2: ...t come into contact with the rotor and impeller can be injured Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill WARNING...

Страница 3: ...res in place Minding the operating instructions Improper use Using the device in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused b...

Страница 4: ...Direction of air flow A 2 Depth of screw max 10 mm 3 Tightening torque 0 8 0 15 Nm 4 Cable diameter min 6 mm max 12 mm tightening torque 2 0 15 Nm Item no 11391 5 9970 ENG Revision 83823 Release 2015...

Страница 5: ...al box ABS plastic Material of blades Press fitted sheet steel blank sprayed with PP plastic Number of blades 5 Direction of air flow A Direction of rotation Clockwise seen on rotor Type of protection...

Страница 6: ...the data on the type plate agree with the connection data Before connecting the device ensure that the supply voltage matches the operating voltage of the device Only use cables designed for current a...

Страница 7: ...nsure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 3 Cable routing for fans installed upright 4 3 4 Motor protection CAUTION Voltage The devi...

Страница 8: ...ion Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2 x grey PE green yellow Item no 11391 5 9970 ENG Revision 83823 Release 2015 02 24 Page 8 10 ebm papst Mulfing...

Страница 9: ...all screws and screwed cable glands are properly tightened 4 7 Switch on device The device is not to be switched on until it has been installed properly and in accordance with its intended use includ...

Страница 10: ...e energise correct connection see connection diagram Thermal overload protector responded Allow motor to cool off locate and rectify cause of error if necessary cancel restart lock out Unacceptable op...

Отзывы: