ebm-papst A4D420-AU02-02 Скачать руководство пользователя страница 5

Operating instructions

A4D420-AU02-02

Translation of the original operating instructions

3.2 Nominal data

Motor

M4D094-EA

Phase

3~

3~

3~

3~

Nominal voltage / VAC

400

400

400

400

Wiring

Δ

Y

Δ

Y

Frequency / Hz

50

50

60

60

Method of obtaining
data

ml

ml

ml

ml

Valid for approval/
standard

CE

CE

CE

CE

Speed (rpm) / min

-1

1360

1060

1490

970

Power consumption / W

260

185

385

220

Current draw / A

0.52

0.31

0.65

0.37

Max. back pressure / Pa

95

60

110

47

Min. ambient
temperature / °C

-40

-40

-40

-40

Max. ambient
temperature / °C

60

60

60

60

Starting current / A

1.7

0.55

1.57

0.51

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

32.3

30

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

42.3

40

05 Variable speed drive

No

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart ·
HRA 590344
D-74673 Mulfingen

08 Type

A4D420-AU02-02

09 Power consumption P

e

/ kW

0.26

09 Air flow q

v

/ m³/h

3205

09 Pressure increase total p

fs

/

Pa

96

10 Speed (rpm) n / min

-1

1350

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The efficiency values displayed for achieving

conformity with the Ecodesign Regulation EU 327/2011 has been reached with defined air

duct components (e.g. inlet rings). The dimensions must be requested from ebm-papst. If

other air conduction geometries are used on the installation side, the ebm-papst evaluation

loses its validity/the conformity must be confirmed again. The product does not fall within

the scope of Regulation (EU) 2019/1781 due to the exception specified in Article 2 (2a)

(motors completely integrated into a product).

3.4 Technical description

Weight

4.7 kg

Size

420 mm

Motor size

94

Rotor surface

Painted black

Terminal box material

PP plastic

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Number of blades

5

Airflow direction

A

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H2

Ambient temperature
note

Occasional start-up at temperatures
between -40°C and -25°C is permitted.
For continuous operation at ambient
temperatures below -25°C (such as
refrigeration applications), use must be
made of a fan design with special low-
temperature bearings.

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Thermal overload protector (TOP) with
basic insulation

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60034-1 (2010); CE

Approval

CCC; EAC

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. The product is to be protected against UV radiation to
prevent the formation of patches and fading. Changes in color are not a
reason for complaint and are not covered by the warranty. UV radiation
in the frequency range and the intensity of natural solar radiation has no
effect on the technical properties of the products.

Item no. 13916-5-9970 · ENU · Change 257334 · Approved 2022-06-14 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A4D420-AU02-02

Страница 1: ...cal staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The...

Страница 2: ...is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before work...

Страница 3: ...be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fa...

Страница 4: ...ion of air flow A 2 Max clearance for screw 10 mm 3 Tightening torque 1 5 0 2 Nm 4 Cable diameter min 6 mm max 12 mm tightening torque 2 0 3 Nm Item no 13916 5 9970 ENU Change 257334 Approved 2022 06...

Страница 5: ...must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 due to the exception specified in Article 2 2a motors completely integrated into a product 3 4 Technical...

Страница 6: ...nection DANGER Voltage on the device Electric shock Always connect a protective earth first Check the protective earth DANGER Faulty insulation Risk of fatal injury from electric shock Use only cables...

Страница 7: ...g cables for connection Only strip the cable as far as necessary ensuring that the cable gland is sealed and there is no strain on the connections For tightening torques see Chapter 3 1 Product drawin...

Страница 8: ...k on NOTE Lack of motor protection Without motor protection the motor can overheat and suffer damage Connect the thermal overload protector installed in the winding The motors are equipped with therma...

Страница 9: ...tion Y Star connection L1 U1 black L2 V1 blue L3 W1 brown W2 yellow U2 green V2 white TOP 2x gray PE green yellow Item no 13916 5 9970 ENU Change 257334 Approved 2022 06 14 Page 9 12 ebm papst Mulfing...

Страница 10: ...inexpert handling transportation damage and resultant imbalance or be caused by component or structural resonance Speed ranges with excessively high vibration levels and possibly resonant frequencies...

Страница 11: ...d replace it Repair of load bearing or rotating parts is not permitted Operate the fan for 2 hours at maximum speed so that any water that has ingressed can evaporate If cleaning does not eliminate vi...

Страница 12: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...