Operating instructions

A3G990-AD05-03

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G150-IF

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Type of data definition

ml

Speed / min

-1

650

Power input / W

1500

Current draw / A

2.6

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Data according to ErP directive

Installation category

A

Efficiency category

Static

Variable speed drive

Yes

Specific ratio

*

1.00

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Actual

Request
2013

Request
2015

Overall efficiency η

es

44.3

30.6

34.6

Efficiency grade N

49.7

36

40

Power input P

ed

/ kW

1.41

Air flow q

v

/ m³/h

20770

Pressure increase total p

sf

/ Pa

101

Speed n / min

-1

655

Data established at point of optimum efficiency

3.4 Technical features

Mass

30 kg

Size

990 mm

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium, coated in black

Material of blades

Die-cast aluminium

Number of blades

7

Direction of air flow

"V"

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 54

Insulation class

"F"

Humidity class

F4-1

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensate discharge
holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- PFC, passive
- Control input 0-10 VDC / PWM
- Over-temperature protected
electronics / motor
- Alarm relay
- Integrated PID controller
- Input for sensor 0-10 V or 4-20 mA
- Output for slave 0-10 V
- RS485 ebmBUS
- Line undervoltage / phase failure
detection
- Motor current limit
- Soft start
- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Electrical leads

Via terminal box

Motor protection

Reverse polarity and locked-rotor
protection

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

CE

Approval

GOST; VDE; CSA C22.2 Nr.77; UL
2111

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.5 Mounting data

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.6 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

Item no. 50422-5-9970 · Revision 68161 · Release 2009-10-14 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G990-AD05-03

Страница 1: ...operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in...

Страница 2: ...DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected at high speeds causing bodily harm Take appropriate safety measures WARNING Rotating device Lo...

Страница 3: ...arly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sustaining or lifesaving function Operation...

Страница 4: ...1 Direction of air flow V 2 Cable diameter min 4 mm max 10 mm tightening torque 4 0 6 Nm 3 Depth of screw max 25 mm 4 Tightening torque 3 5 0 5 Nm Item no 50422 5 9970 Revision 68161 Release 2009 10...

Страница 5: ...Rotor side Operation mode S1 Motor bearing Ball bearing Technical features PFC passive Control input 0 10 VDC PWM Over temperature protected electronics motor Alarm relay Integrated PID controller In...

Страница 6: ...ther Check the device for transport damage Damaged devices must no longer be installed Install the undamaged device according to your application 4 2 Connecting the electrical system DANGER Electric v...

Страница 7: ...adiness for operation is simultaneously at typical 5 W 4 2 4 Residual current operated device Only universal type B or B RCD protective devices are permitted Like frequency inverters RCD protective de...

Страница 8: ...routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Ill 4 Cable routing for fans installed upright 4 4 Factory settings Factor...

Страница 9: ...te to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input SE...

Страница 10: ...ng off the device during operation Switch on the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Switching off the device for maintenance work...

Страница 11: ...ght clips during cleaning make sure to remove them afterwards Motor does not turn Mechanical blockage Switch off de energise and remove mechanical blockage Mains supply voltage faulty Check mains supp...

Страница 12: ...At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual inspection At least every 6 months Replacement of the device Mounting the connecti...

Отзывы: