ebm-papst A3G910-AO83-03 Скачать руководство пользователя страница 5

Operating instructions

A3G910-AO83-03

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G112-IA

Phase

3~

Nominal voltage / VAC

400

Nominal voltage
range / VAC

380 .. 480

Frequency / Hz

50/60

Method of obtaining
data

ml

Status

prelim.

Speed (rpm) / min

-1

610

Power consumption / W

625

Current draw / A

1.1

Max. back pressure / Pa

85

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

45.5

32.2

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

53.3

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

A3G910-AO83-03

09 Power consumption P

ed

/ kW

0.59

09 Air flow q

v

/ m³/h

11680

09 Pressure increase total p

sf

/

Pa

76

10 Speed (rpm) n / min

-1

615

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

12.4 kg

Size

910 mm

Motor size

112

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum, painted black

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Number of blades

5

Blade pitch

Airflow direction

V

Direction of rotation

Clockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H2

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Output 20 VDC, max. 50 mA
- Output for slave 0-10 V
- Input for sensor 0-10 V or 4-20 mA
- Alarm relay
- Integrated PID controller
- Motor current limitation
- PFC, passive
- RS-485 ebmBUS
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from supply
- Thermal overload protection for
electronics/motor
- Line undervoltage / phase failure
detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Electrical hookup

Terminal box

Motor protection

Thermal overload protector (TOP)
internally connected

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 61800-5-1; CE

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Item no. 50444-5-9970 · ENU · Change 205336 · Approved 2020-07-16 · Page 5 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G910-AO83-03

Страница 1: ...ecialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety hazards associated w...

Страница 2: ...system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devices may cause balancing weights or broken fan blades to be ejected and cause injuries Take app...

Страница 3: ...e In particular operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation...

Страница 4: ...on of air flow V 2 Max clearance for screw 16 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 4 Tightening torque 3 5 0 5 Nm Item no 50444 5 9970 ENU Change 205336 Approved 2020 07...

Страница 5: ...ler combination in a standardized measurement setup 3 4 Technical description Weight 12 4 kg Size 910 mm Motor size 112 Rotor surface Painted black Electronics housing material Die cast aluminum paint...

Страница 6: ...ual to 120 times the rated output of the arrangement 4 CONNECTION AND STARTUP 4 1 Mechanical connection CAUTION Cutting and crushing hazard when removing fan from packaging Carefully remove the device...

Страница 7: ...n circuit must be verified in the end application Depending on the installation situation it may be necessary to connect an additional protective earth conductor by way of the extra protective earth t...

Страница 8: ...not included in scope of delivery into the terminal box First connect the PE protective earth Connect the wires to the corresponding terminals Use a screwdriver to do so When connecting ensure that no...

Страница 9: ...ig 4 Cable routing for fans installed upright 4 4 Factory settings Factory settings made for the device by ebm papst Mode PWM control Group address 1 Fan device address 1 Max PWM 100 Min PWM 0 Save se...

Страница 10: ...evel KL3 2 8 GND Reference ground for control interface SELV KL3 3 7 0 10 V Use control current sensor value input 0 10 VDC impedance 100 k only as alternative to 4 20 mA input SELV KL3 4 10 V Voltage...

Страница 11: ...e for maintenance Switch off the device via the control input Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting...

Страница 12: ...aning To ensure a long service life check the fans regularly for proper operation and soiling The frequency of checking is to be adapted accordingly depending on the degree of soiling DANGER Risk of i...

Страница 13: ...rve the applicable country specific legal regulations with regard to the disposal of products or waste occurring in the various phases of the life cycle The corresponding disposal standards are also t...

Отзывы: