Operating instructions

A3G560-AP68-21

Translation of the original operating instructions

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the data on the nameplate match the connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Ground conductor contact resistance according to EN 61800-5-1

Compliance with the impedance specifications according to EN 61800-5-
1 for the protective earth connection circuit must be verified in the end
application.
Depending on the circumstances of installation, it may be necessary to
connect an additional protective earth conductor to the extra protective
earth terminal on the device.
The protective earth terminal is on the housing and has a ground
conductor symbol and a bore hole.

4.2.2 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically less than 250 mA.

At the same time, the effective power in this operating state
(operational readiness) is typically < 4 W.

4.2.3 Residual current circuit breaker (RCCB)

Only universal residual current devices (type B or B+) are
allowed. As with variable frequency drives, residual current
devices cannot provide personal safety while operating the
device.
When the device's power supply is switched on, pulsed
charging currents from the capacitors in the integrated EMC
filter can lead to the residual current devices tripping without
delay. We recommend the use of residual current circuit
breakers with a trip threshold of 300 mA and delayed tripping
(super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Connecting the cables

The device has external leads.

;

First connect the "PE" (protective earth).

Connect the cables according to your application. When doing so,
observe Chapter 4.5 Connection diagram.

4.3.1 Cable routing

Water must be prevented from reaching the cable exit along the cable.

Fans installed lying flat

Fig. 1: Fan installed lying flat, cable routed in a U-shaped loop.

;

Make sure the cable is routed in a U-shaped loop.

;

Avoid kinks or bends in the bushing.

Fans installed upright

Fig. 2: Cable routing for fans installed upright.
The cables must always be routed downward.

4.4 Factory settings

Factory settings made for the device by ebm-papst.

Mode

PWM control

Group address

01

Fan/device address

01

Max. PWM / %

100

Min. PWM / %

0

Save set value to
EEPROM

No

Set value requirement

Analog

Direction of action

Positive (heating)

Item no. 50429-5-9970 · ENU · Change 89187 · Approved 2016-04-14 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G560-AP68-21

Страница 1: ...itably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 B...

Страница 2: ...the rotor or the impeller Secure the device against accidental contact Before working on the system machine wait until all parts have come to a standstill DANGER Ejected parts Missing protective devic...

Страница 3: ...r operating the device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Operation in medical equipment w...

Страница 4: ...m 1 Direction of air flow V 2 Clearance for screw 12 16 mm 3 Cable PVC AWG18 5x crimped ferrules 4 Cable PVC AWG22 3x crimped ferrules Item no 50429 5 9970 ENU Change 89187 Approved 2016 04 14 Page 4...

Страница 5: ...ed at optimum efficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 8 7 kg Fan size 560 mm Rotor surface P...

Страница 6: ...lt Ensure that the device is securely positioned at its place of installation until all fastening screws have been tightened 4 2 Electrical connection DANGER Voltage on the device Electric shock Alway...

Страница 7: ...perating state operational readiness is typically 4 W 4 2 3 Residual current circuit breaker RCCB Only universal residual current devices type B or B are allowed As with variable frequency drives resi...

Страница 8: ...eak for failure 2 A max 250 VAC min 10 mA AC1 1 6 NC white 2 Floating status contact break for failure 2 8 0 10 V yellow Control input set value 0 10 VDC impedance 100 k SELV 2 11 10 VDC red Voltage o...

Страница 9: ...ion detection error An automatic restart follows Blocked rotor After the blockage is removed the motor restarts automatically Line undervoltage line voltage outside of permitted nominal voltage range...

Страница 10: ...t operates an environmental management system which is certified in accordance with ISO 14001 and rigorously implemented around the world on the basis of German standards Right from the development st...

Страница 11: ...spose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 50429 5 9970 ENU Change 89187 Approved 2016 04...

Отзывы: