Operating instructions

A3G500-AN33-03

Translation of the original operating instructions

During the connection work, ensure that no cables splice off.

Fig. 2: Connecting the wires to terminals

;

Insert the strands until they meet resistance.

;

Seal the terminal box.

4.3.3 Cable routing

No water may penetrate along the cable in the direction of the cable gland.

Fans installed lying flat

Make sure that the cable is routed in the form of a loop (water trap).

Fig. 3: Fan installed lying flat, cable routed as a water trap.

Fans installed in upright position

When routing the cable, ensure that the screwed cable glands are
arranged at the bottom. The cables must always be routed downwards.

Fig. 4: Cable routing for fans installed upright.

4.4 Factory settings

Factory settings with which the device is pre-set by ebm-papst.

Operation mode

PWM controlling

Group adress

1

Fan / device adress

1

Max. PWM / %

100

Min. PWM / %

0

Save set value to
EEPROM

Yes

Set value control

Analog

Control function

Positive (heating)

Item no. 50313-5-9970 · Revision 82547 · Release 2014-05-08 · Page 8 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G500-AN33-03

Страница 1: ...install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re ev...

Страница 2: ...contact Before working on the system machine wait until all parts have come to a standstill DANGER Flying parts Missing safety devices may cause balancing weights or broken fan blades to be ejected a...

Страница 3: ...evice in the following ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Operation in medical equipment with a life sust...

Страница 4: ...1 Direction of air flow V 2 Depth of screw max 16 mm 3 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm 4 Tightening torque 3 5 0 5 Nm Item no 50313 5 9970 Revision 82547 Release 2014 05...

Страница 5: ...est Condensate discharge holes Rotor side Operation mode S1 Motor bearing Ball bearing Technical features Output 10 VDC max 10 mA Output 20 VDC max 50 mA Output for slave 0 10 V Input for sensor 0 10...

Страница 6: ...our application 4 2 Connecting the electrical system DANGER Electric voltage on the device Electric shock Always install a protective earth first Check the protective earth DANGER Incorrect insulation...

Страница 7: ...n the mains cable can be measured even when the motor is at a standstill and the mains voltage is switched on The values lie in a range of typical 250 mA The effective power in this operating state re...

Страница 8: ...a water trap Fans installed in upright position When routing the cable ensure that the screwed cable glands are arranged at the bottom The cables must always be routed downwards Fig 4 Cable routing f...

Страница 9: ...cient 10 V equate to 100 level control coefficient KL3 2 8 GND Reference mass for control interface SELV KL3 3 7 0 10 V Use control actual value input 0 10 VDC impedance 100 k only as alternative to 4...

Страница 10: ...remove any that are found Apply the nominal voltage to the voltage supply Start the device by changing the input signal 4 8 Switching off the device Switching off the device during operation Switch of...

Страница 11: ...ical blockage Mains supply voltage faulty Check mains supply voltage restore power supply Important The error message resets automatically The device starts up again automatically without advance warn...

Страница 12: ...accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the device for damage to blades and housing Visual ins...

Отзывы: