ebm-papst A3G500-AD01-58 Скачать руководство пользователя страница 2

Operating instructions

A3G500-AD01-58

Translation of the original operating instructions

WARNING
Terminals and connections have voltage even with a
unit that is shut off

Electric shock
→ Wait five minutes after disconnecting the voltage at all poles

before opening the device.

CAUTION
In the event of failure, there is electric voltage at the
rotor and impeller

The rotor and impeller are base insulated.
→ Do not touch the rotor and impeller once they are installed.

CAUTION
If control voltage is applied or a speed setpoint is stored,
the motor will restart automatically, e.g. after a mains
failure.

Risk of injury
→ Keep out of the device hazard zone.
→ When working on the device, switch off the mains power

and ensure that it cannot be switched back on.

→ Wait until the device stops.
→ After working on the device, remove any tools used or

other objects from the device.

1.5 Safety and protective functions

DANGER
Guard missing and guard not functioning

Without a guard there is a risk of serious injury, for instance
when reaching into the device during operation. Loose parts or
items of clothing could be drawn in.
→ The device is a built-in component. As the operator, you are

responsible for ensuring that the device is secured
adequately.# Operate the device only with a fixed protective
device and guard grille.

→ Stop the device immediately if a protective device is

found to be missing or ineffective.

1.6 Electromagnetic radiation

Interference from electromagnetic radiation is possible, e.g. in conjunction
with open and closed-loop control devices.
If unacceptable emission intensities occur when the fan is installed,
appropriate shielding measures have to be taken by the user.

NOTE
Electrical or electromagnetic interferences after
integrating the device in installations on the customer's
side.

→ Verify that the entire setup is EMC compliant.

1.7 Mechanical movement

DANGER
Rotating device

Body parts that come into contact with the rotor and impeller
can be injured.
→ Secure the device against accidental contact.
→ Before working on the system/machine, wait until all

parts have come to a standstill.

WARNING
Rotating device

Long hair, dangling items of clothing, jewellery and similar items
can become entangled and be pulled into the device. Risk of
injury.
→ Do not wear any loose-fitting or dangling clothing or jewellery

while working on rotating parts.

→ Protect long hair with a cap.

1.8 Emission

WARNING
Depending on the installation and operating conditions,
a sound pressure level greater than 70 dB(A) may arise.

Danger of noise-induced hearing loss
→ Take appropriate technical safety measures.
→ Protect operating personnel with appropriate safety

equipment, e.g. hearing protection.

→ Also observe the requirements of local agencies.

1.9 Hot surface

CAUTION
High temperature at the electronics housing

Risk of burns
→ Ensure sufficient contact protection.

1.10 Transport

NOTE
Transporting the device

→ Transport the device in its original packaging only.

1.11 Storage

;

Store the device, partially or fully assembled, in the original
packaging in a clean, dry and weatherproof place free of vibrations.

;

Protect the device against environmental effects and dirt until final
installation.

;

We recommend storing the device for no longer than one year in
order to guarantee trouble-free operation and longest possible service
life.

;

Even devices explicitly intended for outdoor use are to be stored as
described prior to commissioning.

;

Maintain the storage temperature, see
chapter 3.6 Transport and storage conditions.

;

Please make sure that all screwed cable glands are fitted with
dummy plugs.

Item no. 50607-5-9970 · ENG · Revision 211129 · Release 2020-05-21 · Page 2 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G500-AD01-58

Страница 1: ...st run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once it is installed in the e...

Страница 2: ...Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be injured Secure the device against acc...

Страница 3: ...Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from the customer system...

Страница 4: ...Direction of air flow V 2 Depth of screw max 10 mm 3 Tightening torque 1 5 0 2 Nm 4 Cable diameter min 4 mm max 10 mm tightening torque 2 5 0 4 Nm Item no 50607 5 9970 ENG Revision 211129 Release 2020...

Страница 5: ...ncy The ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 5 8 kg Size 500 mm Motor size 84 Surface of rotor Coated in bl...

Страница 6: ...t resistant safety gloves CAUTION The blades of the impeller could be damaged Set down the fan carefully on a soft surface Make sure the blades are not subjected to load After installation make sure t...

Страница 7: ...50 mA At the same time the effective power in this operating state operational readiness is typically 4 W 4 2 3 Residual current operated device If the use of a residual current device RCD is required...

Страница 8: ...s is not possible a drip edge can be produced by fitting a cable tie directly in front of the cable gland for example Fans installed lying flat Make sure that the cable is routed in the form of a loop...

Страница 9: ...inal operating instructions 4 5 Connection screen Item no 50607 5 9970 ENG Revision 211129 Release 2020 05 21 Page 9 13 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938 81...

Страница 10: ...to devices which have already been equipped with plugs and terminals or similar connectors by the customer WARNING Hot motor housing Fire hazard Ensure that no combustible or flammable materials are...

Страница 11: ...ance in rotating parts Clean the device if imbalance is still evident after cleaning replace the device If you have attached any weight clips during cleaning make sure to remove them afterwards Motor...

Страница 12: ...osal For ebm papst environmental protection and resource preservation are top priority corporate goals ebm papst operates an environmental management system which is certified in accordance with ISO 1...

Страница 13: ...ploying the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 50607 5 9970 ENG Revision 211129 Release 2020 05 21 Page 13 13 ebm papst Mulfing...

Отзывы: