background image

Operating instructions

A3G450-AC28-51

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G084-FA

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 277

Frequency / Hz

50/60

Type of data definition

ml

Speed (rpm) / min

-1

1300

Power input / W

345

Current draw / A

2.2

Max. back pressure / Pa

125

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Running at free air

cs = Customer specs · cu = Customer unit

Subject to alterations

3.3 Data in accordance with ecodesign regulation EU 327/
2011

Actual

Request 2015

01 Overall efficiency η

es

/ %

42.6

30.7

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

51.9

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
rating plate on the product.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
County court Stuttgart · HRA 590344
D-74673 Mulfingen

08 Type

A3G450-AC28-51

09 Power input P

ed

/ kW

0.34

09 Air flow q

v

/ m³/h

4005

09 Pressure increase total p

sf

/

Pa

118

10 Speed (rpm) n / min

-1

1305

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data definition with optimum efficiency. The ErP data is determined using a motor-impeller

combination in a standardised measurement configuration.

3.4 Technical features

Mass

4.8 kg

Size

450 mm

Motor size

84

Surface of rotor

Coated in black

Material of electronics
housing

Die-cast aluminium

Material of blades

Press-fitted sheet steel blank, sprayed
with PP plastic

Number of blades

5

Direction of air flow

V

Direction of rotation

Counter-clockwise, seen on rotor

Type of protection

IP54

Insulation class

"B"

Humidity (F) /
environmental
protection class (H)

H2

Mounting position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

Rotor-side

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 1.1 mA
- Alarm relay
- Motor current limit
- PFC, passive
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Over-temperature protected
electronics / motor
- Line undervoltage detection

Touch current acc.
IEC 60990 (measuring
network Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Thermal overload protector (TOP) wired
internally

Cable exit

Variable

Protection class

I (if protective earth is connected by
customer)

Product conforming
to standard

EN 61800-5-1; CE

Approval

CSA C22.2 no. 77 + CAN/CSA-
E60730-1; CCC; EAC; UL 1004-3 +
60730-1

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

;

Use the device in accordance with its protection type.

Item no. 50718-5-9970 · ENG · Revision 225336 · Release 2020-12-03 · Page 5 / 12

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G450-AC28-51

Страница 1: ...evice to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from the device must be re evaluated once i...

Страница 2: ...installations on the customer s side Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Body parts that come into contact with the rotor and impeller can be...

Страница 3: ...and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Resonance mode operation with heavy vibrations These also include vibrations that are transmitted from...

Страница 4: ...1 Direction of air flow V 2 Thread reach 8 10 mm 3 Connection line PVC AWG18 5x core end sleeve 4 Connection line PVC AWG22 3x core end sleeve Item no 50718 5 9970 ENG Revision 225336 Release 2020 12...

Страница 5: ...he ErP data is determined using a motor impeller combination in a standardised measurement configuration 3 4 Technical features Mass 4 8 kg Size 450 mm Motor size 84 Surface of rotor Coated in black M...

Страница 6: ...it by the centre of the blades only Make sure to avoid any shock Wear safety shoes and cut resistant safety gloves CAUTION The blades of the impeller could be damaged Set down the fan carefully on a...

Страница 7: ...sured even when the motor is at a standstill and the mains voltage is switched on The values are typically in the range 250 mA At the same time the effective power in this operating state operational...

Страница 8: ...nwards 4 4 Factory settings Factory settings with which the device is pre set by ebm papst Operation mode PWM controlling Group adress 01 Fan device adress 01 Max PWM 100 Min PWM 0 Save set value to E...

Страница 9: ...inal operating instructions 4 5 Connection screen Item no 50718 5 9970 ENG Revision 225336 Release 2020 12 03 Page 9 12 ebm papst Mulfingen GmbH Co KG Bachm hle 2 D 74673 Mulfingen Phone 49 0 7938 81...

Страница 10: ...sure to disconnect the earth wire connection last 5 INTEGRATED PROTECTIVE FUNCTIONS The integrated protective functions cause the motor to switch off automatically in case of faults described in the t...

Страница 11: ...for cleaning Completely remove any cleaning agents used Immediately switch off and replace the device if severe corrosion is apparent at load bearing or rotating parts Repairs to load bearing or rota...

Страница 12: ...components are heavy These components could drop off during disassembly This can result in fatal or serious injury and material damage Secure components before unfastening to stop them falling 6 3 3 C...

Отзывы: