ebm-papst A3G400-BK13-P1 Скачать руководство пользователя страница 5

Operating instructions

A3G400-BK13-P1

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G084-DF

Nominal voltage / VDC

110

Nominal voltage
range / VDC

77 .. 138

Method of obtaining
data

ml

Speed (rpm) / min

-1

1670

Power consumption / W

460

Current draw / A

4.2

Max. back pressure / Pa

170

Min. ambient
temperature / °C

-40

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Technical description

Weight

4.32 kg

Size

400 mm

Motor size

84

Rotor surface

Painted black

Electronics housing
material

Die-cast aluminum, painted black

Impeller material

PA plastic UL94 V0

Number of blades

5

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP55

Insulation class

"F"

Moisture (F) /
Environmental (H)
protection class

H3

Installation position

Shaft horizontal or rotor on bottom; rotor
on top on request

Condensation
drainage holes

On rotor side

Mode

S1

Motor bearing

Ball bearing; (sealed)

Technical features

- Output 10 VDC, max. 10 mA
- Operation and alarm display
- Alarm relay
- Motor current limitation
- RS-485 MODBUS-RTU
- Soft start
- EEPROM write cycles: 100,000
maximum
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Overvoltage detection
- Thermal overload protection for
electronics/motor
- Line undervoltage detection
- Reverse polarity protection

Motor protection

Thermal overload protector (TOP)
internally connected

with cable

Lateral

Protection class
assignment

I; If a protective earth is connected by
the customer
This component for installation may
have several local protection classes.
This information relates to this
component’s basic design.
The final protection class is based on
the component’s intended installation and
connection.

Conformity with
standards

EN 15085-1, CPC3: 2013; EN 45545-2,
HL3: 2013 + A1:2015; EN 50155: 2008;
EN 61373, Cat. 1B: 2010; CE

Approval

EAC

Comment

If voltage (e.g. 230 VAC) is passed
through the alarm relay, the SELV signal
wires lose their property of reinforced
insulation, meaning they then have only
basic insulation
The SELV property (reinforced
insulation) is not lost when voltages of up
to 110 VDC are passed through the
alarm relay.

;

Use the device in accordance with its degree of protection.

Information on surface quality

The surfaces of the products conform to the generally applicable industrial
standard. The surface quality may change during the production period.
This has no effect on strength, dimensional stability and dimensional
accuracy.
The color pigments in the paints used perceptibly react to UV light over
the course of time. The product is to be protected against UV radiation to
prevent the formation of patches and fading. Changes in color are not a
reason for complaint and are not covered by the warranty. UV radiation
in the frequency range and the intensity of natural solar radiation has no
effect on the technical properties of the products.

3.4 Mounting data

Any further mounting data required can be taken from the product
drawing or Section Chapter 4.1 Mechanical connection.

Strength class of
screws

8.8

For screw clearance, see Chapter 3.1 Product drawing

;

Secure the screws against unintentional loosening (e.g. use self-
locking screws).

3.5 Transport and storage conditions

Max. permitted
ambient temp. for
motor (transport/
storage)

+80 °C

Min. permitted
ambient temp. for
motor (transport/
storage)

-40 °C

Item no. 53893-5-9970 · ENU · Change 246756 · Approved 2022-01-19 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G400-BK13-P1

Страница 1: ...ed and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1...

Страница 2: ...mpliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accidental contact Before working on th...

Страница 3: ...he device in the following ways is prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibr...

Страница 4: ...3 Cable halogen free railway application EN 45545 4G 1 5 mm 3x wire end ferrule 1x wire not routed externally 4 Cable halogen free railway application EN 45545 7x 0 5 mm 7x wire end ferrule Item no 53...

Страница 5: ...sign The final protection class is based on the component s intended installation and connection Conformity with standards EN 15085 1 CPC3 2013 EN 45545 2 HL3 2013 A1 2015 EN 50155 2008 EN 61373 Cat 1...

Страница 6: ...rallel Electric shock risk of injury Ensure sufficient protection against accidental contact Before working on the electrical hookup short the supply and PE connections CAUTION Voltage The fan is a bu...

Страница 7: ...s made for the device by ebm papst Mode parameter set 1 PWM control Mode parameter set 2 PWM control Fan device address 01 Max PWM 100 Min PWM 10 Save set value to EEPROM No Set value requirement Anal...

Страница 8: ...contact contact rating 250 VAC 30 VDC max 2 A AC1 min 1 mA 5 VDC reinforced insulation on control interface side basic insulation on supply side in accordance with EN 50124 1 2 8 0 10 V yellow Analog...

Страница 9: ...e from the power supply When disconnecting be sure to disconnect the ground connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perform any repairs on your device Send the d...

Страница 10: ...over for intactness or damage Visual inspection At least every 6 months Repair or replacement of device Device for damage to blades and housing Visual inspection At least every 6 months Replacement of...

Страница 11: ...xternal rotor motors from ebm papst Mulfingen GmbH Co KG Ferrite magnets can be disposed of in the same way as normal iron and steel Electrical insulating materials on the product in cables and wires...

Отзывы: