background image

Operating instructions

A3G350-AN01-03

Translation of the original operating instructions

3.2 Nominal data

Motor

M3G074-CF

Phase

1~

Nominal voltage / VAC

230

Nominal voltage
range / VAC

200 .. 240

Frequency / Hz

50/60

Method of obtaining
data

ml

Speed (rpm) / min

-1

1475

Power consumption / W

165

Current draw / A

1.35

Max. back pressure / Pa

100

Min. ambient
temperature / °C

-25

Max. ambient
temperature / °C

60

ml = Max. load · me = Max. efficiency · fa = Free air

cs = Customer specification · ce = Customer equipment

Subject to change

3.3 Data according to Commission Regulation (EU) 327/
2011

Actual

Req. 2015

01 Overall efficiency η

es

/ %

39.9

28.7

02 Measurement category

A

03 Efficiency category

Static

04 Efficiency grade N

51.2

40

05 Variable speed drive

Yes

06 Year of manufacture

The year of manufacture is specified on the
product's rating label.

07 Manufacturer

ebm-papst Mulfingen GmbH & Co. KG
Amtsgericht (court of registration) Stuttgart
· HRA 590344
D-74673 Mulfingen

08 Type

A3G350-AN01-03

09 Power consumption P

ed

/ kW

0.16

09 Air flow q

v

/ m³/h

2400

09 Pressure increase total p

sf

/

Pa

87

10 Speed (rpm) n / min

-1

1495

11 Specific ratio

*

1.00

12 Recycling/disposal

Information on recycling and disposal is
provided in the operating instructions.

13 Maintenance

Information on installation, operation and
maintenance is provided in the operating
instructions.

14 Additional components

Components used to calculate the energy
efficiency that are not apparent from the
measurement category are detailed in the
CE declaration.

*

Specific ratio = 1 + p

fs

/ 100 000 Pa

Data obtained at optimum efficiency level. The ErP data is determined using a motor-impeller

combination in a standardized measurement setup.

3.4 Technical description

Weight

2.1 kg

Size

350 mm

Motor size

74

Blade material

Press-fitted sheet steel blank, sprayed
with PP plastic

Number of blades

5

Airflow direction

V

Direction of rotation

Counterclockwise, viewed toward rotor

Degree of protection

IP54

Insulation class

"B"

Moisture (F) /
Environmental (H)
protection class

H1

Installation position

Any

Condensation
drainage holes

None, open rotor

Cooling hole/opening

On rotor side

Mode

S1

Motor bearing

Ball bearing

Technical features

- Output 10 VDC, max. 10 mA
- Tach output
- Power limiter
- Motor current limitation
- Soft start
- Control input 0-10 VDC / PWM
- Control interface with SELV potential
safely disconnected from the mains
- Overvoltage detection
- Thermal overload protection for
electronics/motor
- Line undervoltage detection

Touch current
according to IEC
60990 (measuring
circuit Fig. 4, TN
system)

<= 3.5 mA

Motor protection

Electronic motor protection

with cable

Variable

Protection class

I (with customer connection of protective
earth)

Conformity with
standards

EN 60335-1; CE

Approval

CSA C22.2 No. 77 + CAN/CSA-
E60730-1; CCC; UL 1004-7 + 60730-1

With regard to cyclic speed loads, note that the rotating parts of
the device are designed for a maximum of one million load
cycles. If you have special questions, consult ebm-papst for
support.

;

Use the device in accordance with its degree of protection.

Item no. 51540-5-9970 · ENU · Change 208645 · Approved 2019-10-23 · Page 5 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A3G350-AN01-03

Страница 1: ...nly authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety haz...

Страница 2: ...y that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device against accide...

Страница 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Страница 4: ...Direction of air flow V 2 Max clearance for screw 10 mm 3 Cable PVC 3G AWG20 3x crimped splices 4 Cable PVC 4x AWG22 4x crimped splices Item no 51540 5 9970 ENU Change 208645 Approved 2019 10 23 Page...

Страница 5: ...000 Pa Data obtained at optimum efficiency level The ErP data is determined using a motor impeller combination in a standardized measurement setup 3 4 Technical description Weight 2 1 kg Size 350 mm M...

Страница 6: ...y avoid shocks Wear safety shoes and cut resistant safety gloves NOTE Damage to the device from vibration Bearing damage shorter service life The fan must not be subjected to force or excessive vibrat...

Страница 7: ...earth conductor by way of the extra protective earth terminal provided on the device 4 2 2 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emission a...

Страница 8: ...12 PE green yellow Ground connection 2 0 10V PWM yellow 0 10 V PWM control input Ri 100 k SELV 4 Tach white Tach output open collector 1 pulse per revolution Isink max 10 mA SELV 3 10 V red Fixed volt...

Страница 9: ...g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRATED PROTECTIVE FEATURES The...

Страница 10: ...ll bearings is designed for a service life of 40 000 hours If bearing replacement is necessary after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure...

Страница 11: ...num Non ferrous metal e g motor windings Plastics particularly with brominated flame retardants in accordance with marking Insulating materials Cables and wires Electronic scrap e g circuit boards Onl...