Operating instructions
A2E200-AH86-75
Translation of the original operating instructions
4.3.1 Cable routing
Water must be prevented from reaching the cable exit along the cable.
NOTE
Damage caused by moisture penetration.
Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable
glands, the cable should be routed in a U-shaped loop
wherever possible.# If this is not possible, a drip edge can
be produced by fitting a cable tie directly in front of the cable
gland for example.
Fans installed upright
Fig. 1: Cable routing for fans installed upright. The cables must always
be routed downward.
Item no. 16023-5-9970 · ENU · Change 96928 · Approved 2017-10-26 · Page 7 / 10
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com