ebm-papst A2D200-AA02-19 Скачать руководство пользователя страница 7

Operating instructions

A2D200-AA02-19

Translation of the original operating instructions

4.3 Connection in terminal box

4.3.1 Preparing cables for connection

Only strip the cable as far as necessary, ensuring that the cable gland is
sealed and there is no strain on the connections. For tightening torques,
see Chapter 3.1 Product drawing.

NOTE
Tightness and strain relief are dependent on the cable
used.

→ This must be checked by the user.

4.3.2 Connecting wires to terminals

;

Route the wire(s) (not included in scope of delivery) into the terminal
box.

;

First connect the "PE" (protective earth).

;

Connect the wires to the corresponding terminals.

Use a screwdriver to do so.
When connecting, ensure that no wire ends fan out.

;

Seal the terminal box.

4.3.3 Cable routing

Water must be prevented from reaching the cable gland along the cable.

NOTE
Damage caused by moisture penetration.

Moisture can penetrate into the terminal box if water is
constantly present at the cable glands.
→ To prevent the constant accumulation of water at the cable

glands, the cable should be routed in a U-shaped loop
wherever possible.

→ If this is not possible, a drip edge can be produced by

fitting a cable tie directly in front of the cable gland for example.

Fans installed lying flat

Make sure the cable is routed in a U-shaped loop.

Fig. 2: Fan installed lying flat, cable routed in a U-shaped loop.

Fans installed upright

When routing the cable, make sure that the cable glands are located at
the bottom. The cables must always be routed downward.

Fig. 3: Cable routing for fans installed upright.

4.3.4 Motor protection

WARNING
Device has no overheating protection

The device is supplied without any automatic overheating
protection. The device can become hot and catch fire.
→ For the version without thermal overload protector, also

install a suitable motor protection switch.

Item no. 15912-5-9970 · ENU · Change 256796 · Approved 2022-05-11 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A2D200-AA02-19

Страница 1: ...d otherwise used by suitably qualified trained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electri...

Страница 2: ...e Long hair and dangling items of clothing jewelry and the like can become entangled and be pulled into the device Injuries can result Do not wear any loose fitting or dangling clothing or jewelry whi...

Страница 3: ...be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration transmitted to the fa...

Страница 4: ...ng All dimensions in mm 1 Direction of air flow A 2 Max clearance for screw 5 mm 3 Cable PVC 4G 0 5 mm 4x splice Item no 15912 5 9970 ENU Change 256796 Approved 2022 05 11 Page 4 11 ebm papst Mulfinge...

Страница 5: ...1 motor does not have factory installed overheating protection CE Use the device in accordance with its degree of protection Information on surface quality The surfaces of the products conform to the...

Страница 6: ...environment Only connect the device to circuits that can be switched off with an all pole disconnection switch 4 2 1 Requirements Check whether the information on the nameplate matches the connection...

Страница 7: ...is constantly present at the cable glands To prevent the constant accumulation of water at the cable glands the cable should be routed in a U shaped loop wherever possible If this is not possible a d...

Страница 8: ...se motor Y Star connection 1 Counterclockwise operation L1 V1 blue L2 U1 black L3 W1 brown 2 Clockwise operation L1 U1 black L2 V1 blue L3 W1 brown PE green yellow Item no 15912 5 9970 ENU Change 2567...

Страница 9: ...device from the power supply at the supply line s main switch When disconnecting be sure to disconnect the ground connection last 5 MAINTENANCE MALFUNCTIONS POSSIBLE CAUSES AND REMEDIES Do not perfor...

Страница 10: ...ion At least every 6 months Replace device Abnormal bearing noise acoustic At least every 6 months Replace device 5 3 Disposal For ebm papst environmental protection and resource preservation are top...

Страница 11: ...ectrolytic capacitors Dispose of electronic components employing the proper procedures for electronic scrap Please contact ebm papst for any other questions on disposal Item no 15912 5 9970 ENU Change...

Отзывы: