ebm-papst A1G300-AE33-52 Скачать руководство пользователя страница 5

Operating instructions

A1G300-AE33-52

Translation of the original operating instructions

3.2 Nominal data

Motor

M1G074-CF

Nominal voltage in VDC

48

Nominal voltage
range in VDC

36 .. 57

Type of data definition

fa

Speed in min

-1

1800

Power input in W

90

Current draw in A

2.0

Max. back pressure in Pa

105

Min. ambient
temperature in °C

-25

Max. ambient
temperature in °C

60

ml = max. load · me = max. efficiency · fa = running at free air

cs = customer specs · cu = customer unit

Subject to alterations

3.3 Technical description

Mass

2.15 kg

Size

300 mm

Surface of rotor

Coated in black

Material of blades

Sheet steel, coated in black

Number of blades

7

Direction of air flow

"A"

Direction of rotation

Clockwise, seen on rotor

Type of protection

IP 42

Insulation class

"B"

Humidity class

F0

Mounting position

Any

Condensate discharge
holes

None

Operation mode

S1

Motor bearing

Ball bearing

Technical features

- Tach output
- Motor current limit
- Soft start
- Control input 0-10 VDC / PWM

Motor protection

Reverse polarity and locked-rotor
protection

Cable exit

Variable

Product conforming
to standard

EN 60950-1

Approval

UL 1004-1; CSA C22.2 Nr.77

For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.4 Mounting data

For depth of screw, see chapter 3.1 Graphic rendition of products

;

Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).

Strength class for
mounting screws

8.8

You can obtain additional mounting data from the product drawing if
necessary.

3.5 Transport and storage conditions

;

Use the device in accordance with its protection type.

Max. permissible
ambient motor temp.
(transp./ storage)

+80 °C

Min. permissible
ambient motor temp.
(transp./storage)

-40 °C

3.6 Electromagnetic compatibility

EMC interference
immunity

Acc. to EN 61000-6-2 (industrial
environment)

EMC interference
emission

Acc. to EN 55022 (Class B)

Item no.: 50992-5-9970 · Revision: 72357 · Print-out: 2012-04-11 · Y. Uhlmann (VM-TDO) · Page 5 / 9

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 7938 81-0 · Fax +49 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание A1G300-AE33-52

Страница 1: ...st personnel are permitted to transport unpack assemble operate or maintain the device or to use it in any other manner 1 3 Basic safety rules 1 1 3 Basic safety rules Any safety hazards stemming from...

Страница 2: ...e come to a standstill WARNING Rotating device Long hair loose items of clothing and jewellery could become entangled and pulled into the device You could be injured Do not wear any loose clothing or...

Страница 3: ...lowing ways is particularly prohibited and may cause hazards Operating the device with an imbalance e g caused by dirt deposits or icing Moving air that contains abrasive particles Moving highly corro...

Страница 4: ...sures have the unit mm 1 Direction of air flow A 2 Depth of screw max 6 mm 3 Connection line AWG20 4 x brass lead tips crimped Item no 50992 5 9970 Revision 72357 Print out 2012 04 11 Y Uhlmann VM TDO...

Страница 5: ...rity and locked rotor protection Cable exit Variable Product conforming to standard EN 60950 1 Approval UL 1004 1 CSA C22 2 Nr 77 For cyclic speed loads note that the rotating parts of the device are...

Страница 6: ...y environment Operate the device with a safely isolated power pack 4 2 1 Prerequisites Check whether the data on the type plate agree with the connection data Before connecting the device ensure that...

Страница 7: ...residual ripple 3 5 1 2 PWM lin yellow PWM lin control input 0 10 V 1 3 DUE white Speed monitoring output 3 pulses per rotation Isink max 10 mA 1 4 GND blue Reference mass Item no 50992 5 9970 Revisio...

Страница 8: ...n with a unit that is shut off Electric shock Wait five minutes after disconnecting the voltage at all poles before opening the device CAUTION If control voltage is applied or a speed setpoint is stor...

Страница 9: ...ich measure Check the protective casing against accidental contact for damage and to ensure that it is intact Visual inspection At least every 6 months Repair or replacement of the device Check the de...

Отзывы: