3. TECHNICAL DATA

3.1 Product drawing

All dimensions in mm.

1

Installed position: shaft horizontal (install support struts only vertically as illustrated) or rotor on bottom; rotor on top on request

2

Cable PVC AWG18
6x wire-end ferrule

3

Cable PVC AWG22
5x wire-end ferrule

4

Inlet ring with pressure tap (k-factor: 115)

5

Fastening holes for FlowGrid 25310-2-2957 (not included in scope of delivery) are provided and must be subsequently opened as required

Item no. 1170000711 · ENU · Change 230626 · Approved 2022-10-28 · Page 4 / 13

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание 8300100053

Страница 1: ...rained and authorized technical staff Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules...

Страница 2: ...rmissible radiation levels occur following installation appropriate shielding measures have to be taken by the user NOTE Electrical or electromagnetic interference after installing the device in custo...

Страница 3: ...enance work Conveying air at an ambient air pressure between 800 mbar and 1050 mbar Using the device within the permitted ambient temperature range see Chapter 3 6 Transport and storage conditions and...

Страница 4: ...op on request 2 Cable PVC AWG18 6x wire end ferrule 3 Cable PVC AWG22 5x wire end ferrule 4 Inlet ring with pressure tap k factor 115 5 Fastening holes for FlowGrid 25310 2 2957 not included in scope...

Страница 5: ...geometries are used on the installation side the ebm papst evaluation loses its validity the conformity must be confirmed again The product does not fall within the scope of Regulation EU 2019 1781 d...

Страница 6: ...neer or operator owner of the device to ensure if necessary after consultation with the network operator that this device is only connected to a connection point with an Ssc value greater than or equa...

Страница 7: ...pply matches the device voltage Only use cables designed for the current level indicated on the nameplate For determining the cross section note the sizing criteria according to EN 61800 5 1 The prote...

Страница 8: ...f residual current circuit breakers RCCB with a trip threshold of 300 mA and delayed tripping super resistant characteristic K 4 2 5 Leakage current For asymmetrical power systems or if a phase fails...

Страница 9: ...rating 250 VAC 2 A AC1 min 10 mA reinforced insulation on supply side and basic insulation on control interface side 2 8 0 10V yellow Analog input set value 0 10 V Ri 100 k adjustable curve SELV 2 10...

Страница 10: ...m permissible vibration severity must not exceed 3 5 mm s and should be checked at intervals of 6 months It is to be determined at the motor mount at the motor support plate at least in axial directio...

Страница 11: ...lty Check line voltage restore power supply Attention The error message resets automatically Device restarts automatically without warning Faulty connection Isolate from supply correct connection see...

Страница 12: ...ssary after that period contact ebm papst Adapt the maintenance intervals to the actual level of dust exposure 6 3 Safety inspection NOTE High voltage test The integrated EMC filter has Y capacitors T...

Страница 13: ...ic Metallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings P...