Operating instructions

D3G146-HQ13-34

Translation of the original operating instructions

CAUTION
Voltage

The device is a built-in component and has no disconnecting
switch.
→ Only connect the device to circuits that can be switched off

with an all-pole disconnection switch.

→ When working on the device, secure the system/

machine in which the device is installed so as to prevent it
from being switched back on.

NOTE
Water ingress into wires or cables

Water ingress at the customer end of the cable can damage the
device.
→ Make sure the end of the cable is connected in a dry

environment.

Only connect the device to circuits that can be switched off with
an all-pole disconnection switch.

4.2.1 Requirements

;

Check whether the information on the nameplate matches the
connection data.

;

Before connecting the device, make sure the power supply matches
the device voltage.

;

Only use cables designed for the current level indicated on the
nameplate.
For determining the cross-section, note the sizing criteria according
to EN 61800-5-1. The protective earth must have a cross-section
equal to or greater than that of the phase conductor.
We recommend the use of 105 °C cables. Ensure that the minimum
cable cross-section is at least
AWG 26 / 0.13 mm².

Protective earth contact resistance according to EN 60335

Compliance with the resistance specifications according to EN 60335 for
the protective earth connection circuit must be verified in the end
application. Depending on the installation situation, it may be necessary
to connect an additional protective earth conductor by way of the extra
protective earth terminal provided on the device.

4.2.2 Reactive currents

Because of the EMC filter integrated for compliance with EMC
limits (interference emission and immunity to interference),
reactive currents can be measured in the supply line even
when the motor is at a standstill and the line voltage is switched
on.

The values are typically in the range < 250 mA

At the same time, the effective power in this operating state
(operational readiness) is typically < 4 W.

4.2.3 Residual current circuit breaker (RCCB)

If the use of a residual current device (RCD) is required in your
installation, only pulse-current sensitive and/or AC/DC-
sensitive residual current devices (type A or B) are
permissible. As with variable frequency drives, residual current
devices cannot provide personal safety while operating the
device. When the device power supply is switched on, pulsed
charging currents from the capacitors in the integrated EMC
filter can lead to the instant tripping of residual current devices.

We recommend the use of residual current circuit breakers
(RCCB) with a trip threshold of 300 mA and delayed tripping
(super-resistant, characteristic K).

4.2.4 Locked-rotor protection

Due to the locked-rotor protection, the starting current (LRA) is
equal to or less than the nominal current (FLA).

4.3 Plug connection

4.3.1 Making supply connections

;

Check your connector's pin assignment.

;

Connect the built-in connector with the mating connector.

;

Ensure that the connector is properly engaged.

Item no. 52429-5-9970 · ENU · Change 200696 · Approved 2020-03-16 · Page 7 / 11

ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · [email protected] · www.ebmpapst.com

Содержание 2748470

Страница 1: ...f Only authorized specialists are permitted to install the device to carry out a test run and to perform work on the electrical installation 1 3 Basic safety rules 1 1 3 Basic safety rules The safety...

Страница 2: ...ent Verify that the entire setup is EMC compliant 1 7 Mechanical movement DANGER Rotating device Risk of injury to body parts coming into contact with the rotor or the impeller Secure the device again...

Страница 3: ...prohibited and could be hazardous Operating the device in an unbalanced state e g due to dirt deposits or ice formation Resonant operation operation with severe vibration This also includes vibration...

Страница 4: ...8230 120 Ms 1 1 10 V 1 2 Tach 1 3 0 10 V PWM 1 4 GND 2 Macromodul connector Stocko MSLO 9404 003 00A 960 pluggable with Stocko MFMP 9761 003 50A 960 2 1 L 2 2 N 2 3 PE 3 4x sheet metal nut for thread...

Страница 5: ...sing material PP plastic Motor suspension Motor vibration damped on both sides Direction of rotation Counterclockwise viewed toward rotor Degree of protection IP10 Insulation class F Moisture F Enviro...

Страница 6: ...m vibration e g using compensators or similar elements Ensure stress free attachment of the fan to the substructure Check the device for transport damage Damaged devices are not to be installed Instal...

Страница 7: ...ective earth conductor by way of the extra protective earth terminal provided on the device 4 2 2 Reactive currents Because of the EMC filter integrated for compliance with EMC limits interference emi...

Страница 8: ...10 V max 1 1mA red Voltage output 10 V 1 1 mA electrically isolated not short circuit proof CON11 11 2 Tacho white Tach output Open collector 1 pulse per revolution electrically isolated Isink max 10...

Страница 9: ...t Do not switch the motor e g in cyclic operation on and off via power supply Disconnect the device from the power supply When disconnecting be sure to disconnect the ground connection last 5 INTEGRAT...

Страница 10: ...ning does not eliminate vibrations the fan may need to be rebalanced To have it rebalanced contact ebm papst The fan is equipped with maintenance free ball bearings The lifetime lubrication of the bal...

Страница 11: ...tallic materials are generally considered to be fully recyclable Separate the components for recycling into the following categories Steel and iron Aluminum Non ferrous metal e g motor windings Plasti...