Test protocol 

(Foil 48 V)

Installation performed by: 

 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

according to the attached material specification.

Date 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Signature: 

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

The facility documented with photo/sketch

Minimum insulation value 10 M

Ω

. The foil lacks soil. Measure between the foil and a grounded object.

*

Tolerance -5 % - +10 %

First calculate the length 69/53 cm foil to 43 cm foil according 

to formula 2/3. Then calculate the theoretical resistance value 

according to formula 1. Enter the resistance value and the 

length in the test report.

72

Total length (m)

Theoretical resistance value

=

48 V, 80 W/m², width 43 cm

Formula 1

Test protocol

Length 69 cm-width (.............. m) x1,65 = 

Length 43 cm-width = 

(.............. m)

 +

Total length

Add the lengths together and enter the total length in formula 1.

(.............. m)

(.............. m)

Ebeco Foil 48 V: Recalculate all the foil 43 cm-width:

Formula 2

After fixation

After flooring

Product

Resistance value* 

(

Ω

)

Insulation value* 

(M

Ω

)

Resistance value* 

(

Ω

)

Insulation value* 

(M

Ω

E-nr: .....................  
Installed length: 
........................ (m)
E-nr: .....................  
Installed length: 
........................ (m)

Formula 3

Length 53 cm-width (.............. m) x1,25 = 

Length 43 cm-width = 

(.............. m)

 +

Total length

Add the lengths together and enter the total length in formula 1.

(.............. m)

(.............. m)

Ebeco Foil 48 V 53 cm: Recalculate all the foil 43 cm-width:

Содержание Foil 48 V

Страница 1: ...SE ASSEMBLY INSTRUCTIONS Ebeco Foil 48 V garantera ebeco se Create warranty certificate directly in the mobile phone ...

Страница 2: ......

Страница 3: ...d or wooden floors the floor must normally be reinforced with plasterboard putty or the like according to current industry regulations Concrete floors are sanded For concrete floors with a risk of moisture this system is not suitable as the glue can dissolve and the foil is damaged In wet rooms the foil must be placed under the moisture barrier The foil must be protected against mechanical damage ...

Страница 4: ...ansformer size calculation Adhesive 89 601 90 Coating only applies to tiles as surface coating In addition to Ebeco Foil you also need Preparations for your placement Article number Article E 520 70 11 Transformer 250 VA E 520 70 13 Transformer 350 VA Calculation of the size of the transformers Number of meters 43 width x 32 Number of meters 53 width x 40 Number of meters 69 width x 53 Sum xx mini...

Страница 5: ...d apart as the temperature differences become noticeable This applies especially to plastic carpet Part of the transparent border approx 15 mm wide can be cut off but at least 5 mm must remain It is important to get the best coverage on the surfaces where you are standing e g in front of kitchen furniture or wash basins Plan so that the foil is placed against the outer wall to minimize cold drafts...

Страница 6: ...the foils firmly against the floor with a rubber scraper Let the glue dry Leave about 10 cm at the connection ends these parts are glued after the connection pins are mounted Adjust the crimping pliers E 89 606 90 In order for the pressing of the clamps to be correct the tongs must be set correctly On compressed seaweed sheep the opening does not exceed 1 3 mm Adjust by loosening the screw and tur...

Страница 7: ...onnect the foil lengths De insulate approx 6 mm and insert the cables into the connection clamp With only one cable the stripped part is folded double according to Fig 11 Clamp the cables with the crimping tool according to Fig 12 fig 12 fig 11 fig 13 Install the connection clamps Thread the clip onto the foil and center it over the copper tape Clamp the clamp with your fingers according to Fig 9 ...

Страница 8: ...cal value with the measured value Tolerance on resistance values 5 to 10 Insulation test the foils and enter the value in the test report that you find on the next page Document the installation with a photo according to the instructions on the warranty certificate Gluing the plastic mat Spread glue all over the floor Pull out glue with a smooth rubber scraper over the foil so that the holes are f...

Страница 9: ...n the test report 72 Total length m Theoretical resistance value 48 V 80 W m width 43 cm Formula 1 Test protocol Length 69 cm width m x1 65 Length 43 cm width m Total length Add the lengths together and enter the total length in formula 1 m m Ebeco Foil 48 V Recalculate all the foil 43 cm width Formula 2 After fixation After flooring Product Resistance value Ω Insulation value MΩ Resistance value ...

Страница 10: ...EBECO AB Lärjeågatan 11 415 02 Göteborg SWEDEN Phone 46 31 707 75 50 ebeco se info ebeco se Manual Foil 48V Eng 55218 221117 ...

Отзывы: