ALARM X13
INTERNAL ERROR

There is no communication between the 
control panel with the button pad and 
display, and the power plate screwed 
into the radiator.
Internal fault in the frequency converter.

Check that the flat cable that 

communicates both electronic circuits 

are well connected and tightened.

It may be due to an occasional error in 

the firmware of the frequency converter 

or the spot reading of a parameter 

deemed to be outside of the limits. In 

this case we recommend cutting the 

power to the frequency converter for 

a few minutes. If after a few minutes, 

when the power is reconnected to 

the frequency converter, the message 

remains, contact your nearest technical 

service.

MESSAGE

REASONS

SOLUTION(S)

16. MAINTENANCE AND REPAIR

We recommend monitoring the frequency inverter periodically and regulating its operation.

17. WARRANTY

Failure to comply with the instructions provided in this instruction manual and/or any manipulation of the inverter 
not carried out by an authorized technical service and/or the use of non-original spare parts will invalidate the 
warranty and exempt the manufacturer from any liability in case of accidents to people or damage to property 
and/or to the product itself.
Once the product has been received, check that it has not suffered significant breaks or dents. Otherwise, inform 
the delivery person. Once the frequency inverter has been removed from its packaging, check that it has not been 
damaged in transit. In the event of any damage, inform the distributor.
Check that the characteristics displayed on the rating plate are those you requested.
If fault is found which is not included in the “TROUBLESHOOTING” table, contact the nearest authorized dealer.

18. DISPOSAL AND ENVIRONMENTAL ASPECTS

To dispose of the parts that comprise the frequency converter, you must abide by the current regulations and laws 
of the country where the product is used. In any event, do not throw away parts that may pollute the environment. 

This symbol on the product indicates that it should not be disposed of with other household waste.

This stipulation only refers to the disposal of equipment within the European Union (2012/19 /EU). It is the user’s 
responsibility to dispose of the equipment by delivering it to a designated collection point for the recycling and 
disposal of electrical equipment. For more information about equipment collection points, contact your local waste 
disposal agency.

Содержание E-SPD Series

Страница 1: ...QL L vQWUH LQHUH 423 RO XOODQ P YH EDN P N ODYX X 451 TR 3 25 47 69 91 113 135 157 179 201 223 INVERTER FOR PUMPS Instruction and maintenance manual INVERTER PER ELETTROPOMPE Manuale di istruzioni e m...

Страница 2: ......

Страница 3: ...on and assembly 8 Electrical connections 9 Screen format 10 Main screen 11 Operation mode 12 Start upwizard 13 Setup menu 14 Warning management 15 Alarms 16 Maintenance and repair 17 Warranty 18 Dispo...

Страница 4: ...al sensory or mental capabilities or without the due experience or knowledge except if a person responsible for their safety has explained the instructions and supervised their operation of their freq...

Страница 5: ...ts of use Minimum ambient temperature 10 C Maximum ambient temperature 40 C Variation in the supply voltage 10 Humidity range 5 to 95 without condensation and vapor Maximum altitude 2 000 meters The a...

Страница 6: ...according to the regulations in force in the country in question A table with the maximum recommended lengths according to the cross section of the electrical cable can be found below Each interface c...

Страница 7: ...rt adapter parts 5 and 11a provided Break the 3 holes of the metal radiator of the power circuit part 4 with a screwdriver The 3 holes are visible on the inside of the radiator add the image Screw the...

Страница 8: ...485 COMUNICATION FRONT PANEL U V W TT3 MT2 MOTOR 230 400Vac MOTOR 230 400Vac MT2 230Vac 1 N R POWER SUPPLY TT3 400Vac 3 S T 8 ELECTRICAL CONNECTIONS B A B A E SPD MT 2200 E SPD TT 4000 It is necessary...

Страница 9: ...requency converter is giving a voltage output its maximum load is 9 W You can connect any potential free contact that will perform the functions programmed in parameters 5 12 and 5 13 respectively to...

Страница 10: ...isplay Manual stop button Right selection button Lower button Raise button Left selection button Alarm LED H z 4 8 9 4 8 8 A m p 0 8 3 0 8 9 B a r 0 5 5 0 5 5 1 4 5 7 M e n u Current rotation frequenc...

Страница 11: ...stablished working pressure In contrast when the demand for flow decreases the frequency converter makes the electric motor rotate more slowly so the pressure of the water network remains unaffected b...

Страница 12: ...ase the value that is blinking and use F2 to change to the next value The sequence of values is DAY MONTH YEAR HOUR MINUTES The lower left part of the display indicates the day of the week calculated...

Страница 13: ...e is always within the working curve of the pump and always try to avoid the extremes of the curve in other words with flows near 0 or very low pressures Validate this with F2 F2 Once you have reached...

Страница 14: ...ot be displayed The stop frequency calculated is indicated this is for the working pressure indicated when the pump drops below this frequency it does not generate any flow so the motor then stops Pre...

Страница 15: ...7 MINIMUM WORKING FREQUENCY 5 08 MAXIMUM WORKING FREQUENCY 5 09 AUXILIARY OPERATING FREQUENCY 5 10 MINIMUM AUXILIARY OPERATING DELAY 5 11 MINIMUM AUXILIARY STOP DELAY 5 12 DIGITAL INPUT 1 5 13 DIGITAL...

Страница 16: ...onnected to an electricity grid 2 04 HOURS WORKED Hours This indicates the total number of hours worked providing an output voltage of the frequency converter 2 05 START UP NUMBER This indicates the t...

Страница 17: ...00 5 06 PRINCIPAL STOP DELAY Sec Time from the moment the main pump is working at a speed below the stop frequency parameter 1 4 until it stops fully ATTENTION Improper use of manual mode can cause ov...

Страница 18: ...remotely OFF The relay is never activated Alarm NO The relay closes before an alarm Alarm NC The relay opens before an alarm Running The relay is energised when the unit is running External stop The r...

Страница 19: ...after the 24 hour notice is detected again dry running the drive will lock indefinitely until you press F2 5 1 99 5 23 LOW WATER LEVEL ALARM DELAY Sec Time from when the system calculates a low water...

Страница 20: ...he RUN LED blinks The frequency converter is in the process of stopping the pump WARNING REASON EXPLANATION SOLUTION 14 WARNING MANAGEMENT One of the main principles of the frequency converter is to t...

Страница 21: ...ng the stop frequency setup wizard again 5 24 If this warning persists after running the wizard again you must reduce the working pressure as the pump that is connected will not be able to reach it Th...

Страница 22: ...it is assembled on a wall mount ensure the fan of the mount functions correctly when the motor is running ALARM F04 INPUT VOLTAGE The frequency converter is not receiving electric current of is outsi...

Страница 23: ...ng at a very low pressure and at a speed high for a time Check that the water network has no leaks greater than those required for regular demand ALARM A10 TIME PARAMETERS The stop delays of the auxil...

Страница 24: ...r from any liability in case of accidents to people or damage to property and or to the product itself Once the product has been received check that it has not suffered significant breaks or dents Oth...

Отзывы: