EBARA Submersible Semi-vortex Sewage Pumps

DVSU/DVSHU

Operating, Installation, and Maintenance

Troubleshooting

CAUTION

All service should be done by factory trained or qualified personnel only.

Trouble

Cause

Remedy

Does not start.

(1) Power failure

(1)-(3) Contact electric power company; devise counter-measures

Starts, but 

(2) Large discrepancy between power source and voltage

immediately stops.

(3) Significant drop in voltage
(4) Motor phase malfunction

(4) Inspect connections and magnetic switch

(5) Electric circuit connection faulty 

(5) Inspect electric circuit

(6) Faulty connection of control circuit 

(6) Correct wiring

(7) Blown fuse 

(7) Replace with correct type of fuse

(8) Faulty magnetic switch

(8) Replace with correct type of magnetic switch

(9) Water is not at level indicated by float

(9) Raise water level

(10) Float is not in appropriate level 

(10) Move float to an appropriate starting level

(11) Float defective 

(11) Repair or replace

(12) Short circuit breaker is functioning 

(12) Repair location of short circuit

(13) Foreign matter clogging pump 

(13) Remove foreign matter

(14) Motor burned out 

(14) Repair or replace

(15) Motor bearing broken  

(15) Repair or replace

Operates, but stops

(1) Prolonged dry operation has activated motor protector (1) Raise stop water level

after a while.

and caused pump to stop
(2) High liquid temperature has activated motor protector

(2) Lower liquid temperature

and caused pump to stop

Does not pump.

(1) Reverse rotation 

(1) Correct rotation (see Operation 2, (3))

Inadequate volume.

(2) Significant drop in voltage  

(2) Contact electric power company and devise 
counter-measures

(3) Operating a 60Hz pump on 50Hz 

(3) Check nameplate

(4) Discharge head is high

(4) Recalculate and adjust

(5) Large piping loss 

(5) Recalculate and adjust

(6) Low operating water level causes air suction    

(6) Raise water level or lower pump

(7) Leaking from discharge piping 

(7) Inspect, repair

(8) Clogging of discharge piping 

(8) Remove foreign matter

(9) Foreign Matter in suction inlet  

(9) Remove foreign matter

(10) Foreign matter clogging pump 

(10) Disassemble and remove foreign matter

(11) Worn impeller  

(11) Replace impeller

Over current  

(1) Unbalanced current and voltage  

(1) Contact electric power company and devise counter-measure

(2) Significant voltage drop

(2) Contact electric power company and devise counter-measure

(3) Motor phase malfunction 

(3) Inspect connections and magnetic switch

(4) Operating 50HZ pump on 60Hz 

(4) Check nameplate

(5) Reverse rotation 

(5) Correct rotation (see Operation 2)

(6) Low head; excessive volume of water  

(6) Replace pump with low head pump

(7) Foreign matter clogging pump

(7) Disassemble and remove foreign matter

(8) Motor bearing is worn or damaged

(8) Replace bearing

Pump vibrates;

(1) Reverse rotation 

(1) Correct rotation

excessive operating 

(2) Pump clogged with foreign matter 

(2) Disassemble and remove foreign matter

noise.

(3) Piping resonates 

(3) Improve piping

(4) Gate valve is closed too far  

(4) Open gate valve

Single phase motor:

(1)  Defective start capacitor

(1) Replace start capacitor.

Motor hums, but will not  

(2) Defective relay:

run, over load trips.

a) Check relay coil with continuity meter

(2a) Replace relay if open coil is found

In approximately 15-20 

b) Check for loose or broken connection in relay and

(2b) If circuit is intact, replace start capacitor and restart motor

seconds. After an off  

start capacitor circuit 

time of 30-60 seconds,

c) If after step (2b) motor fails to start, check with  

(2c) If no continuity is indicated, replace relay

overload protector will

continuity indicator across terminal 162

reclose. If motor again

(3) Defective motor; if motor fails to start after replacing 

(3) Check motor for electrical and mechanical defects 

hums and overload trips, 

relay (start or run capacitor if used), motor may be

the fault is probably due to defective
either a defective start 
capacitor or relay, or 
perhaps the motor itself.

CALL 1-800-577-8111 FOR SALES AND SUPPORT

Содержание DVSHU

Страница 1: ...ersible Semi Vortex Sewage Pump Model DVSU Model DVSHU Operating Instructions Installation Maintenance Manual EBARA Fluid Handling EBARA International Corporation CALL 1 800 577 8111 FOR SALES AND SUP...

Страница 2: ...septic gaseous or possible septic sump Do not work under heavy suspended objects unless there is a positive support under it to stop its fall in event of sling or hoist failure Disregard of this warni...

Страница 3: ...t the impeller turns smoothly by hand 2 Precautions when operation is suspended 1 If operation is to be suspended for 30 days with the pump immersed in water measure the insulation resistance of the m...

Страница 4: ...wn 8 Non automatic pumps model DVSU DVSHU do not have an automatic operating system based on built in floats Do not operate the pump for a long time with the water level near the minimum operating lev...

Страница 5: ...ctrical work should be performed by a qualified electrician and all national and local electrical codes must be observed Three Phase Model DVSU E GREEN U RED V WHITE W BLACK PR PROTECTOR AUTO CUT L1 R...

Страница 6: ...e activated Constant repetition of this action will shorten pump service life Do not start the pump again in such a situation until after the motor has completely cooled 2 Test Operation 1 Model DVSU...

Страница 7: ...e mechanical seal can be prolonged by replacing the oil in the mechanical seal chamber once a year When replacing the oil lay the pump on its side with filler plug on top as shown in Fig 5 For model D...

Страница 8: ...scharge piping 7 Inspect repair 8 Clogging of discharge piping 8 Remove foreign matter 9 Foreign Matter in suction inlet 9 Remove foreign matter 10 Foreign matter clogging pump 10 Disassemble and remo...

Страница 9: ...0 A48 Class 30 AISI420 A283 Grade D AISI304 AISI304 AISI304 AISI304 NO FOR 1 UNIT 1 1 1 1 1 1 1 1 1 1 1 1 2 3 or 4 4 3 or 4 PART NO 174 193 219 801 802 811 814 816 830 842 848 849 1 849 2 865 915 PART...

Страница 10: ...30 AISI420 A283 Grade D AISI304 AISI304 AISI304 AISI304 AISI304 NO FOR 1 UNIT 1 1 1 1 1 1 1 1 2 1 1 1 4 4 4 4 1 PART NO 135 174 193 200 801 802 811 814 816 817 830 842 848 849 1 849 2 915 PART NAME WA...

Страница 11: ...Purchaser No allowance will be made for repairs without EIC s written consent or approval and the Warranty Period shall not be suspended upon stopping operation for warranty repairs nor recommence up...

Страница 12: ...Contact your dealer or supplier for more information about other EBARA products CALL 1 800 577 8111 FOR SALES AND SUPPORT...

Отзывы: