Lithium (LiFePo4)
Battery Owners Manual
Battery Packs Covered
12V96Ah
24V72Ah
36V72Ah
48V72Ah
12V144Ah
24V144Ah
36V105Ah
48V105Ah
12V216Ah
24V300Ah
48V160Ah
12V288Ah
48V320Ah
12V600Ah
WARNING!
•Always wear safety glasses when working with any type of battery
•Do not short circuit the battery terminals
•Do not connect the battery terminals with reverse polarity
•Do not charge more than 1C or 175A max (C=amp hours of the battery pack)
•Do not continuously discharge more than 1C or 175A max (C=amp hours of the battery pack)
•Do not momentarily discharge more than 600A for 3 seconds
•Do not momentarily discharge more than 300A for 30 seconds
•Do not open the battery pack for any reason, there is a risk of electric shock.
•Do not connect batteries in series to obtain a higher voltage pack.
•Do not connect more than 3 batteries in parallel
•Only parallel connect battery packs of identical voltage, capacity, and age
Storage
Charge at least every six months
If storing unused for extended periods, disconnect loads and store at 50% state of charge
If storing unused for extended periods, store at room temperature
Installation
Make sure the battery pack voltage is correct for the application.
Do not connect with reverse polarity.
Always secure battery pack in place with mounting strap or battery hold down kit
Use only M8 or 5/16 ring terminals
Torque terminal bolts to 150-155 in/ft - Do not over tighten
If an inverter or DC-DC voltage converter will be used, connect battery terminals prior to
connecting an inverter or converter. Terminal arc damage is not covered under warranty.