5 Installation
5.4 Mounting
42
MICRO PANEL XV400 5.7"/8.4"
12/2014 MN04802009Z-EN
www.eaton.com
5.4.2
Mounting a device with standard front
1
Select the mounting position of the device as described in Chapter 5.2.2 Requirements for the
mounting position,
2
Prepare a mounting cutout for the device at the selected position:
Mounting cutout:
5.7" devices: 198
142 mm (±1 mm)
8.4" devices: 261
194 mm (±1 mm)
Material thickness at the mounting cutout 2…5 mm
3
Insert the sealing strip supplied in the groove (A) on the rear of the device front plate and cut it so
that the join is tight.
An additional set of retaining brackets is required for mounting in accordance with IP65
and for use in potentially explosive atmospheres. Please contact your supplier.
Abb. 23 Mounting cutout for 5.7" devices
Abb. 24 Mounting cutout for 8.4" devices
CAUTION
Poor sealing
Poor sealing resulting from the twisting of the sealing strip or due to a gap between
the ends of the sealing strip.
The join of the sealing strip must be positioned on the bottom of the device.
Do
not
twist the sealing strip when it is inserted.
Cut the sealing strip to a suitable length so that the join is tight.
198.0