4. External connections
4.5 Serial interfaces for communication with PLCs or devices
4.5.1.1 Wiring topic
l
Shielded cables must be used.
l
The maximal baud rate depends on the cable length
Cable length
Max. baud rate
2,5 m
115200 Bit/s
5 m
57600 Bit/s
10 m
38400 Bit/s
15 m
19200 Bit/s
30 m
9600 Bit/s
Tab. 11: RS-232 cable length based on baud rate
When preparing connections, ensure that the cable shield has a low
impedance connection with the connector housing.
XV360 Single Touch Display
07/19 MN048025EN www.eaton.eu
51