5 Installation
5.3 Interfaces
Touch display XV-102
10/2020 MN04802004Z-EN
Eaton.com
25
5.3
Interfaces
WARNING
Stray currents
Large transient currents between the protective circuits of different devices may re-
sult in fire or in malfunctions due to signal interference.
If necessary, a potential equalization conductor should be installed parallel to the
cable. This should have a cross-section that is a multiple of the cable screen.
CAUTION
Interference
The values specified in the technical data and the device's electromagnetic compat-
ibility (EMC) cannot be guaranteed if unsuitable cables, improperly assembled and
terminated cables, and/or unprofessional wiring are used.
Only use cables prefabricated and terminated by professionals.
The cables being used must be assembled and terminated as required by the
port/interface description in this document.
When wiring the device, follow all instructions regarding how to wire the corre-
sponding port/interface.
All general Directives and standards must be complied with.
CAUTION
Non-galvanically-isolated interfaces
The device may be damaged by potential differences.
The GND terminals of all bus modules must be connected.
Содержание XV-102 Series
Страница 1: ...Manual XV 102 Touch display 10 2020 MN04802004Z EN ...
Страница 6: ...Content 4 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...
Страница 22: ...3 Safety regulations 3 4 Device specific hazards 20 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...
Страница 24: ...4 Operating and indication elements 4 1 Overview 22 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...
Страница 60: ...6 Operation 6 4 Inserting and removing the SD card 58 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...
Страница 64: ...7 Maintenance and repairs 7 4 Troubleshooting 62 Touch display XV 102 10 2020 MN04802004Z EN Eaton com ...