38
Eaton xStorage 400 Installation and Operation Manual P-164001032—Rev 01
55..33
C
Chhaarrggiinngg M
Mooddee
When select programmable conditions are met, the xStorage 400 will charge its internal batteries. Three-
phase, 480 VAC electrical current flows into the xStorage 400 from the utility and is converted to DC
current by the EnergyAware Inverters.
The current then flows to the batteries and the batteries will continue to charge until the
programmed maximum State-of-Charge (SOC).
Figure 23. Path of Current Through xStorage 400 — Charging Mode
AC Input /
Output
DC - DC
Converter
Battery
Energy Conversion Modules (ECMs)
Inverter
Main Power Flow
(Charging)
Trickle Current
Energized
Digital Metering and
Environmental Controls
and Systems Power
Environmental
Controls/Systems
Digital Metering
Содержание xStorage 400
Страница 6: ...vi Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Table of Contents...
Страница 8: ...viii Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Figures...
Страница 10: ...x Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Tables...
Страница 32: ...22 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Inspecting and Unpacking...
Страница 56: ...46 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Hydrogen Mitigation Procedure...
Страница 66: ...56 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Predict Pulse Dashboard...
Страница 86: ...76 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Warranty...
Страница 95: ...Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 85 Battery Safety Data Sheets...
Страница 96: ...P 16400103201 P 164001032 01...