Eaton xStorage 400 Installation and Operation Manual P-164001032—Rev 01
17
Figure 11. xStorage 400 Center of Gravity — Top View
Dimensions are in millimeters [inches]
1536.7 [60.50]
865.9 [34.09]
TOP VIEW
33..22..22..11 S
Syysstteem
m A
Anncchhoorriinngg P
Prreeppaarraattiioonn
•
For standard installations, use eight anchors.
•
For installations utilizing a side entrance wiring kit, seven anchors may be used to reduce interference with
conduit.
•
Anchors shall be HILTI
®
KB-TZ2 or equivalent.
•
Anchors shall be 3/4" in diameter and embedded a minimum of 3 3/4" into a 3000 psi concrete slab of 6"
thickness or greater.
•
Distance from anchor to nearest slab edge shall be minimum of 10".
•
Anchors shall be stainless steel if exposed to wet or damp environments.
Содержание xStorage 400
Страница 6: ...vi Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Table of Contents...
Страница 8: ...viii Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Figures...
Страница 10: ...x Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 List of Tables...
Страница 32: ...22 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Inspecting and Unpacking...
Страница 56: ...46 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Hydrogen Mitigation Procedure...
Страница 66: ...56 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Predict Pulse Dashboard...
Страница 86: ...76 Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 Warranty...
Страница 95: ...Eaton xStorage 400 Installation and Operation Manual P 164001032 Rev 01 85 Battery Safety Data Sheets...
Страница 96: ...P 16400103201 P 164001032 01...