13 Relay output module XN-322-4DO-RNO
13.4 Technical data relay outputs
XN300 slice modules
06/16 MN050002 EN
www.eaton.com
81
Figure 48:
Wiring diagram with U
e
at all four connection terminals
for total currents > 10 A
13.3.2 Suppressor circuit for inductive loads
13.4 Technical data relay outputs
X1
C1
R1
R1
R
L
PE
0 V
F1
U
e
I
B
I
L
X2
C2
R2
R2
R
L
I
B
I
L
X3
C3
R3
R3
R
L
I
B
I
B
I
L
X4
C4
R4
R4
R
L
I
B
I
L
I
max
NOTICE
When switching inductive loads, a snubber must be added at
the load in order to prevent EMI. RC suppressors have proven to
be particularly effective for this purpose as a result of their
dynamic response. In contrast, the use of varistors is not always
adequate.
Number of relay outputs
4
Function
N/O
Rated operational voltage U
e
24 V DC
230 V AC
maximum rated operating voltage
30 V DC
250 V AC
Continuous current per channel I
c
6 A DC
6 A AC
Simultaneity of all outputs
100 %
Continuous current per connector contact
max. 10 A DC
max. 10 A AC
Current-carrying capacity of common contact
link I
B
max. 10 A DC
max. 10 A AC
On-delay/off-delay
≤
10 ms/
≤
10 ms
Switching Frequency
Mechanical switching operations
10 x 10
6
Resistive load / lamp load
2 Hz
Inductive
0.5 Hz
Switching frequency as per IEC 61810
(8A, 250VAC, cos
φ
=1, 85°C)
100x10
3
Making capacity