7 Product-specific CAN objects XN300 slice modules
7.25 XN-322-1CNT-8DIO
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
341
Design of the data bytes:
7.25.13 Encoder Signal Configuration (Object 0x40F6)
Object 0x40F6 is used to configure the counter's encoding.
Design of the data bytes:
Byte 0:
Feature
Description / Value
EDS
Name
CounterValueSDO
[MxSubExt40F5]
ParameterName=CounterValueSDO
ObjectType=0x7
DataType=0x0006
AccessType=ro
PDOMapping=0
Count=1
Description
Encoder Measuring Value
Object Code
ARRAY
Mapping
SDO
Data type
UNSIGNED16
Sub index
01 … FE hex
Access
ro
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B1
5
B1
4
B1
3
B1
2
B1
1
B1
0
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Feature
Description / Value
EDS
Name
SignalConfig
[MxSubExt40F6]
ParameterName= SignalConfig
ObjectType=0x7
DataType=0x0005
AccessType=rw
PDOMapping=0
Count=1
Description
Encoder Signal Configuration
Object Code
ARRAY
Mapping
SDO
Data type
UNSIGNED8
Sub index
01 … FE hex
Access
ro
Byte 0:
Sub index
1
≦
n
≦
254
B7
B6
B5
B4
B3
B2
B1
B0
SignalConfig
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...