Xiria
16
994.570 G01 06
3.2.4
Setting up the unit
The Xiria system has been designed in accordance with
the recommendations set out in IEC 62271-200 which
theoretically prevents internal faults from occurring.
Moreover, when set up correctly, a Xiria unit will comply
with this IEC standard for setting up with an arc channel.
The pressure relief flaps in the Xiria enclosure are located
at the rear and bottom of the unit, and they can be
connected to the arc channel of the building.
The pressure relief flaps at the rear can be sealed off using
a cover plate available separately as an option.
For further information see also the floor plan drawings in
Appendix 1.
The following rules apply to a set-up with an arc channel:
The channel is to be connected to a location where no
danger can occur to personnel.
The bore of the channel is to be a minimum of 0.15 m
2
and the channel itself requires to be capable of
withstanding overpressure of at least 0.5 bar.
The area the arc channel is connected to must be
capable of withstanding the overpressure also.
3.2.5
Securing to the floor
The Xiria unit must be fixed to the floor in four locations.
The drilling pattern for fixing and cable holes is included
in Appendix 1, 'Floor plan'.
Use washers under bolt heads/nuts.
3.3 Connecting the cables
3.3.1
Types of cables
Single-core cables can be connected to the unit.
Three-core cables can be connected, if the dimensions of
the associated splitting point fit into the cable compartment.
See for the available space for cable connection plugs
Table 3.
Table 3: Maximum dimensions for cable connectors inside the Xiria cable compartment
Panel type
Cable compartment type
Door lock
Arc resistant
Non arc
resistant
A (mm)
A (mm)
B (mm)
C (mm)
Circuit-breaker
200 A
Elbow plug connector type A
238
240
36
37
Circuit-breaker
500 A
Bolted T connector type C
195
197
36
37
Circuit-breaker
630 A
Bolted T connector type C
195
197
36
37
Load break switch
630 A
Bolted T connector type C
277
279
36
37
Figure 3-6: Xiria cable compartment
Содержание xiria series
Страница 39: ...Xiria 994 570 G01 06 39 APPENDIX 1 FLOOR PLANS...
Страница 40: ...Xiria 40 994 570 G01 06...
Страница 41: ...Xiria 994 570 G01 06 41...
Страница 42: ...Xiria 42 994 570 G01 06...
Страница 43: ...Xiria 994 570 G01 06 43...
Страница 44: ...Xiria 44 994 570 G01 06...
Страница 45: ...Xiria 994 570 G01 06 45 APPENDIX 2 VOLTAGE DETECTING SYSTEM WEGA...
Страница 46: ...Xiria 46 994 570 G01 06...
Страница 47: ...Xiria 994 570 G01 06 47...
Страница 48: ...Xiria 48 994 570 G01 06 APPENDIX 3 ORION 3 0...
Страница 49: ...Xiria 994 570 G01 06 49 APPENDIX 4 SHORT CIRCUIT INDICATOR...
Страница 55: ...Xiria 994 570 G01 06 55...
Страница 56: ...Xiria 56 994 570 G01 06...