 Effective 11/97 Supersedes I.L. 3778A20A dated March, 1993 

I.L. 3778A74H01

Type VCP-W Manual Ground and Test Device (Complex) 

Figure 1: Type VCP-W Manual Ground and Test Device 

TABLE OF CONTENTS 

1-0

 Introduction ................................................ 1 

1-1

 Description ................................................. 1 

1-2

 Operation ................................................... 2 

WARNING

READ AND UNDERSTAND THESE INSTRUCTIONS 
BEFORE ATTEMPTING TO USE THIS DEVICE. 
IMPROPER USE CAN RESULT IN DEATH, BODILY 
INJURY AND/OR PROPERTY DAMAGE. 

CAUTION

BECAUSE OF THE UNIQUE APPLICATION AND 
VAST VARIETY OF SYSTEM AND USER 
REQUIREMENTS, SPECIFIC OPERATING 
PROCEDURES MUST BE DEVELOPED BY THE 
USER. FAILURE TO DEVELOP THESE 
PROCEDURES COULD LEAD TO IMPROPER USE 
OR OTHER MORE SERIOUS CON-SEQUENCES. 

1-0 INTRODUCTION

Type Vac Clad-W switchgear assemblies are designed 
with all the bus work completely insulated for safety. 
Since the current carrying parts are not readily 
accessible, type VCP-W Manual Ground and Test 
Device is designed for insertion into the breaker 
compartment to gain access to the primary stationary 
contacts. It provides a convenient means to: 

1. Ground a circuit for maintenance work;
2. Apply potential for cable testing; and,
3. Access both bus and line circuits for “phasing out”.

tests.

CAUTION

BECAUSE OF THE UNIQUE APPLICATION AND 
VAST VARIETY OF SYSTEM/USER 
REQUIREMENTS, SPECIFIC SAFE OPERATING 
PROCEDURES FOR THE USE OF THIS DEVICE 
MUST BE DEVELOPED BY THE USER. 

1-1 DESCRIPTION

The device consists of a drawout element that can be 
inserted into a circuit breaker compartment in the same 
manner as a type VCP-W circuit breaker. It includes six 
terminals and ground bus connections. Each terminal is 
isolated from each other and the ground bus connection 
by insulating barriers. The upper and lower terminals are 
accessible upon opening the respective front hinged 
door. The ground connection is located in the lower front 
section of the device. 

Vac Clad-W switchgear is a two-high arrangement. In 
the lower compartment the top terminals normally 
connect to the main bus and the bottom terminals 
normally connect to the incoming line or feeders. In an 
upper compartment, the opposite normally holds true, 
i.e., the top terminals connect to the incoming line or
feeders and the bottom terminals connect to the main
bus. This must be verified for each application. Because
of this two-high arrangement, the bus and the line
positions of the grounding and test device terminals will
vary depending upon whether the device is used in an
upper or lower compartment. Therefore, 

it is most

important that the bus or line terminals be correctly
identified for each compartment before using this
device.

Содержание VCP-W

Страница 1: ... UNIQUE APPLICATION AND VAST VARIETY OF SYSTEM USER REQUIREMENTS SPECIFIC SAFE OPERATING PROCEDURES FOR THE USE OF THIS DEVICE MUST BE DEVELOPED BY THE USER 1 1 DESCRIPTION The device consists of a drawout element that can be inserted into a circuit breaker compartment in the same manner as a type VCP W circuit breaker It includes six terminals and ground bus connections Each terminal is isolated ...

Страница 2: ...evice in a clean dry area free from dust dirt moisture etc Keep all insulating surfaces which include primary support insulation and insulation barriers clean and dry Check all primary circuit connections to make certain that they are clean and tight Permit only authorized trained personnel to use this device Take extreme care while using this device to avoid contacting Live or Hot energized termi...

Страница 3: ...I L 3778A74H01 Pa g e 3 Effective 11 97 Figure 2 Standard Device ...

Страница 4: ...P a g e 4 I L 3778A74H01 Effective 11 97 Figure 3 Device With Bails ...

Страница 5: ...I L 3778A74H01 Pa g e 5 Effective 11 97 Figure 4 Standard Device Upper ...

Страница 6: ...P a g e 6 I L 3778A74H01 Effective 11 97 Figure 5 Standard Device Lower ...

Страница 7: ...I L 3778A74H01 Pa g e 7 Effective 11 97 Figure 6 Device With Bails Upper ...

Страница 8: ...P a g e 8 I L 3778A74H01 Effective 11 97 Figure 7 Device With Bails Lower ...

Страница 9: ...I L 3778A74H01 Pa g e 9 Effective 11 97 Figure 8 Code Plate Legend ...

Страница 10: ...P a g e 10 I L 3778A74H01 Effective 11 97 ...

Страница 11: ...I L 3778A74H01 Pa g e 11 Effective 11 97 ...

Страница 12: ...P a g e 12 I L 3778A74H01 Effective 11 97 ISI Style 3778A74B Printed in U S A Eaton 1000 Cherrington Parkway Moon Township PA 15108 4312 ...

Отзывы: