20
Instruction Booklet
IB02201004E
Effective October 2017
Revision #4
Instructions for installation, operation, and
maintenance of 38 kV type VacClad-W,
150 BIL switchgear indoor housings
EATON
www.eaton.com
B . Securing the transformer drawer to the lifter pan:
1 . Lock the lifter in place by stepping down on the lifter brake
2 . Confirm that the transformer drawer is in the fully retracted
position . The drawer is fully retracted when the upper sec-
tion of the drawer is butted up against the lower section of
the drawer (see Figure 9) .
3 . Roll the drawer onto the lifter pan and up against the rubber
stops . Use the pan rails as a guide (see Figure 27) .
NOTICE
DO NOT HANDLE THE FUSE TUBES AND MATING PARTS WHILE
MOVING THE TRANSFORMER DRAWER. THIS MAY CAUSE DAMAGE
TO THESE PARTS.
Figure 25. Break Pedal for Locking the Lifter.
4 . Make sure the drawer safety latch has secured the drawer
to the lifter pan (Figure 27) . The safety latch hitches to the
underside of the drawer flange . Push on the drawer to con-
firm it is fixed to the pan .
Figure 26. Latching the Transformer to the Lifter Pan.
Figure 27. Releasing the Lifter Brake.