Energizing the Switchgear
Signal Block
(Annunciator)
(Optional)
Protection Relay
Wired Remote
Control Socket
(Optional)
Breaker position
control button
Breaker opening
button and breaker
open signal
Breaker closing
button and breaker
closed signal
Lamp test and
DC lighting button
HMH24-04 Protection and Control Panel
Earthing Switch
Closed
LBS / Disconnector
Open
00
II
0
I
0
I
IF THIS SWITCHGEAR IS USED AS AN
INCOMING FEEDER DO NOT CLOSE
THE EARTING SWITCH BEFORE CUTTING
DOWN THE ENERGY FROM PREVIOUS STATION
!
DO NOT INTERFERE WITH THE EARTHING
MECHANISM WHILE THE LOAD BREAK
SPRING IS CHARGED
!
OPERATIONAL
DIAGRAM
I
0
I
0
0
0
CLOSE
THE SWITCHGEAR
DOOR
OPEN
THE EARTHING
SWITCH
THE SWITCH
DISCONNECTOR
CLOSE
IS THERE ANY
OPERATION ON
THE SWITCHGEAR?
YES
NO
CHARGE
THE SPRING
(DISCONNECTOR)
CHARGE
THE SPRING
(CB)
CLOSE
THE CIRCUIT
BREAKER
OPEN
THE CIRCUIT
BREAKER
THE SWITCH
DISCONNECTOR
OPEN
CLOSE
THE EARTHING
SWITCH
OPEN
THE SWITCHGEAR
DOOR
1.ORGANİZE SANAYİ BÖLGESİ OĞUZ CAD. NO: 6
06935 SİNCAN / ANKARA TÜRKİYE
TEL: +90 312 267 07 12 FAX: +90 312 267 05 17
ULUSOY ELEKTRİK A.Ş.
www
www.eaton.com /
Standar
d
:
IEC 62271-200
Protect on Degree: IP3X
00
II
0
I
0
I
IF THIS SWITCHGEAR IS USED AS AN
INCOMING FEEDER DO NOT CLOSE
THE EARTING SWITCH BEFORE CUTTING
DOWN THE ENERGY FROM PREVIOUS STATION
!
DO NOT INTERFERE WITH THE EARTHING
MECHANISM WHILE THE LOAD BREAK
SPRING IS CHARGED
!
OPERATIONAL
DIAGRAM
I
0
I
0
0
0
CLOSE
THE SWITCHGEAR
DOOR
OPEN
THE EARTHING
SWITCH
THE SWITCH
DISCONNECTOR
CLOSE
IS THERE ANY
OPERATION ON
THE SWITCHGEAR?
YES
NO
CHARGE
THE SPRING
(DISCONNECTOR)
CHARGE
THE SPRING
(CB)
CLOSE
THE CIRCUIT
BREAKER
OPEN
THE CIRCUIT
BREAKER
THE SWITCH
DISCONNECTOR
OPEN
CLOSE
THE EARTHING
SWITCH
OPEN
THE SWITCHGEAR
DOOR
1.ORGANİZE SANAYİ BÖLGESİ OĞUZ CAD. NO: 6
06935 SİNCAN / ANKARA TÜRKİYE
TEL: +90 312 267 07 12 FAX: +90 312 267 05 17
ULUSOY ELEKTRİK A.Ş.
www
www.eaton.com /
Standar
d
:
IEC 62271-200
Protect on Degree: IP3X
Ulusoy HMH24-04 Incoming/Outgoing Switchgear with Circuit Breaker User Manual
www.eaton.com