background image

Tripp Lite by Eaton SmartOnline Series User Guide 614-21325—Rev 01

17

Table 4. LCD Operating Modes (Continued)

UPS Display

Description

IN:120V 60.0HZ

HIGH EFFIC.MODE

The UPS is operating on High Efficiency mode. The UPS is

powering and protecting the equipment

IN:120V 60.0HZ

BYPASS MODE

An overload or a fault has occurred, or a command has been

received, and the UPS is in Bypass mode. Equipment is powered

but not protected by the UPS.

33..33

U

UP

PS

S H

Hoom

mee M

Meennuu

The SmartOnline UPS will display the

Home Menu

by default. The

Home Menu

will display the UPS mode and

contains nine different types of UPS measurements that can be seen by navigating the menu.

Navigate the

Home Menu

by pressing the

or

buttons on the display.

Press the ESC button to return to the first measurement of the

Home Menu

.

Table 5. UPS Home Menu

Display Information

LCD Display

Bottom Row Values

Displays the UPS mode , load percentage

and W.

LOAD:100% 2700W

ONLINE MODE

The LOAD data screen specifies the

amount of power that connected

equipment is currently using in terms of

percentage and Watt.

Displays the UPS mode , load percentage

and VA.

LOAD:100% 3000VA

ONLINE MODE

The OUTPUT LOAD LEVEL screen

indicates the load percentage and VA

output load level.

Displays the UPS mode and output load

power factor.

LOAD:PF=0.99

ONLINE MODE

The OUTPUT LOAD POWER FACTOR

screen indicates the power factor of

connected equipment.

Displays the UPS mode , input voltage

and frequency.

IN:120V 60.0HZ

ONLINE MODE

The INPUT VOLTAGE & FREQUENCY

screen displays current UPS input data.

Displays the UPS mode and output

voltage and frequency.

OUT:120V 60.0HZ

ONLINE MODE

The OUTPUT VOLTAGE & FREQUENCY

screen displays current UPS output data.

Displays the UPS mode , battery voltage

and battery charge percentage.

BATT:50.2V 100%

ONLINE MODE

The BATTERY voltage screen tracks the

charge level of your connected battery

bank in terms of voltage and charge

percentage.

UPS Home Menu

Содержание Tripp Lite SmartOnline Series

Страница 1: ...TXLCD2U SU1000RTXLCD2UN SU1500RTXLCD2U SU1500RTXLCDN SU2200RTXLCD2U SU2200RTXLCDN SU3000RTXLCD2U SU3000RTXLCD2UN SUINT1000LCD2U SUINT1500LCD2U SUINT2200LCD2U SUINT3000LCD2U BP36RT BP48RT BP72RT Rack T...

Страница 2: ...nstruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be requir...

Страница 3: ...tes that waste electrical and electronic equipment as well as waste batteries and accumulators should not be discarded together with unseparated household waste but must be collected separately The pr...

Страница 4: ...es 0 C to 40 C with batteries The system is not for use in a computer room AS DEFINED IN the standard for the Protection of Information Technology Equipment ANSI NFPA 75 US installations only S Sp pe...

Страница 5: ...PS and Extended Battery Pack Tower Installation 13 2 4 4 Extended Battery Pack Tower Connections 14 3 3 I In nt te er rf fa ac ce es s a an nd d C Co om mm mu un niic ca at tiio on n 1 15 5 3 1 Contro...

Страница 6: ...5 4 Replacing batteries 33 5 5 Recycling the used equipment 36 6 6 T Tr ro ou ub blle es sh ho oo ot tiin ng g 3 37 7 6 1 Typical Alarms and Faults 37 6 2 Silencing the Alarm 41 6 3 Service and Suppo...

Страница 7: ...ro ot te ec ct tiio on n Tripp Lite by Eaton has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFC...

Страница 8: ...occur when you least expect it and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of los...

Страница 9: ...42 5 19 3 17 7 x 17 3 x 3 4 450 x 440 x 86 5 SU2200RTXLCD2U SU2200RTXLCDN 61 6 27 9 23 8 x 17 3 x 3 4 605 x 440 x 86 5 SU3000RTXLCD2U SU3000RTXLCD2UN 63 28 6 23 8 x 17 3 x 3 4 605 x 440 x 86 5 SUINT10...

Страница 10: ...itional battery module 5 Primary group outlets for connection of critical equipment 6 Group 1 programmable outlets for connection of equipment 7 Group 2 programmable outlets for connection of equipmen...

Страница 11: ...or to the other battery modules 13 Connectors for automatic recognition of battery modules BP72RT 13 13 12 12 Table 3 UPS Accessories Part number Description BP36RT BP48RT BP72RT Extended Battery Mod...

Страница 12: ...6 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Rear Panels...

Страница 13: ...ervice representative NOTE Check the battery recharge date on the shipping carton label If the date has passed and the batteries were never recharged do not use the UPS Contact your service representa...

Страница 14: ...Safety instructions 21 Quick start 22 Mounting kit for 19 inch enclosures 23 2 supports for tower position Elements supplied depending on the version or optional 26 LXE communication card optional st...

Страница 15: ...control panel to the UPS Do not pull on the cable or disconnect it A small amount of arcing may occur when connecting the internal batteries This is normal and will not harm personnel Connect the cabl...

Страница 16: ...heir final location Figure 7 UPS Tower Install Adjustment of the orientation of the LCD panel and of the logo Figure 8 Adjusting the LCD 2 2 3 3 2 2 U UP PS S R Ra ac ck k I In ns st ta alllla at tiio...

Страница 17: ...tt te er ry y P Pa ac ck k I In ns st ta alllla at tiio on n 2 2 4 4 1 1 E Ex xt te er rn na all B Ba at tt te er ry y R Ra ac ck km mo ou un nt t I In ns st ta alllla at tiio on n The external batte...

Страница 18: ...ur when connecting an external battery pack to the UPS This is normal and will not harm personnel To connect the external battery packs to the UPS 1 Insert the external battery pack cable into the UPS...

Страница 19: ...external battery pack s Figure 11 Rackmount External Battery Pack Connections BP36RT BP48RT BP72RT 2 2 4 4 3 3 U UP PS S a an nd d E Ex xt te en nd de ed d B Ba at tt te er ry y P Pa ac ck k T To ow...

Страница 20: ...e er r C Co on nn ne ec ct tiio on ns s NOTE A small amount of arcing may occur when connecting an external battery pack to the UPS This is normal and will not harm personnel To connect the external b...

Страница 21: ...4 Control Panel Online mode indicator green Fault indicator red Escape Up Down Enter On Off button Battery mode indicator orange Bypass mode indicator orange ONLINE MODE LOAD 100 2700W ESC Indicator S...

Страница 22: ...gure 15 LCD Description LCD mode description Load equipment status ONLINE MODE LOAD 100 2700W ESC The following table describes the status information provided by the UPS Note If other indicator appea...

Страница 23: ...ttom Row Values Displays the UPS mode load percentage and W LOAD 100 2700W ONLINE MODE The LOAD data screen specifies the amount of power that connected equipment is currently using in terms of percen...

Страница 24: ...nuous data on the KWh kilowatt hour that connected equipment has consumed in the last one hour period 3 3 4 4 D Diis sp plla ay y F Fu un nc ct tiio on ns s Press the button from the UPS Home Menu to...

Страница 25: ...menu AUTO START Auto start can be enabled or disabled through this menu START ON BYPASS Start on bypass can be enabled or disabled through this menu SLEEP MODE Sleep mode can be enabled or disabled th...

Страница 26: ...Submenu Submenu Menu Function CONTROL GO TO BYPASS GO BACK NORMAL GO TO BYPASS GO BACK NORMAL GO TO BYPASS command is used to force ups to bypass mode from ONLINE MODE GO BACK NORMAL command is used t...

Страница 27: ...ine UPS to restart automatically when mains recovers after a complete battery discharge AUTO START ENABLED Default ENABLED DISABLED The SmartOnline UPS starts up as soon as mains power is available ST...

Страница 28: ...t that will actuate Output signal parameters through external contact connector INPUT DB9 4 NO Default NO ROO RPO BUILDING ALARM FORCED BYPASS ON GENERATOR SHUTDOWN CMD Delay time and active cannot se...

Страница 29: ...AULT BYPASS UPS OK LOAD PROTECTED LOAD POWERED GENERAL ALARM BAT CHARGING OVLD PREALARM BAT DISCONN Sets events or fault that will actuate Output signal parameters through external contact connector o...

Страница 30: ...tes 3 programmable signal inputs one Remote Power Off RPO input terminal one Remote On Off ROO input terminal one RS 232 input pin 4 Signal inputs can be configured see 3 5 User Settings Settings Com...

Страница 31: ...ty connected circuits Reinforced insulation to the utility is required The RPO switch must be a dedicated latching type switch not tied into any other circuit The RPO signal must remain active for at...

Страница 32: ...ys test the RPO function before applying your critical load to avoid accidental load loss Programmable Signal Outputs The Tripp Lite by Eaton SmartOnlineUPS incorporates 4 programmable signal outputs...

Страница 33: ...tOnlineUPS models have one available communication bay for the following connectivity cards Network card WEBCARDLXE Provides monitoring and control using an SNMP network management platform web browse...

Страница 34: ...events and it notifies you of important UPS or power information If there is a power outage and the SmartOnline UPS battery power becomes low the PowerAlert Software suite can automatically shut down...

Страница 35: ...ta ar rt tiin ng g t th he e U UP PS S o on n B Ba at tt te er ry y NOTE By default the Cold Start or battery start setting is enabled from the factory To start the UPS on battery 1 Press the button o...

Страница 36: ...PS The indicator illuminates Depending on overload conditions the UPS remains in Bypass mode for at least 5 seconds and will stay in this mode if three transfers to Bypass occur within 20 minutes The...

Страница 37: ...ng discharge the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than the setting capacity threshold 0 by default This threshold can be modified Restart battery le...

Страница 38: ...32 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Retrieving the Event Log...

Страница 39: ...date has passed and the batteries were never recharged do not use them Contact your service representative 5 5 3 3 W Wh he en n t to o R Re ep plla ac ce e B Ba at tt te er riie es s Tripp Lite by Eat...

Страница 40: ...battery supplies not having a grounded supply circuit ELECTRIC ENERGY HAZARD Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury Disconnect charging so...

Страница 41: ...xtended battery pack 2 Replace the extended battery pack s See 5 5 Recycling the used equipment for proper disposal A small amount of arcing may occur when connecting an extended battery pack to the U...

Страница 42: ...d acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical o...

Страница 43: ...al UPS Conditions Conditions Possible cause Action Battery mode LED is On 1 beep every 10 seconds A utility failure has occurred and the UPS is in battery mode The UPS is powering the equipment with b...

Страница 44: ...to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any heat sources Allow the UPS to cool Ensure the airflow...

Страница 45: ...UPS has transfered to bypass or stop 706 UPS TEMP FAULT UPS internal temperature is high due to temperature UPS has transfered to bypass or stop 70C MIN INV VOLT Inverter voltage is too low 70D MAX I...

Страница 46: ...t present Please check if batteries are connected rightly or fuse is open 612 BAT TEST ABORTED Battery test condition is not met Check UPS mode is AC online or HE Load must be greater than 10 Battery...

Страница 47: ...local service representative and ask for a UPS technical representative Please have the following information ready when you call for service Model number Serial number Firmware version number Date of...

Страница 48: ...42 Tripp Lite by Eaton SmartOnline Series User Guide 614 21325 Rev 01 Service and Support...

Страница 49: ...VA 675W SU1000RTXLCD2U SU1000RTXLCD2UN 1000VA 900W SU1500RTXLCD2U SU1500RTXLCDN 1500VA 1350W SU2200RTXLCD2U SU2200RTXLCDN 2000VA 1800W SU3000RTXLCD2U SU3000RTXLCD2UN 3000VA 2700W SUINT1000LCD2U 1000VA...

Страница 50: ...CD2U 61 2 27 8 23 8 x 17 3 x 3 4 605 x 440 x 86 5 BP36RT 48 1 21 8 17 7 x 17 3 x 3 4 450 x 440 x 86 5 BP48RT 59 5 27 17 7 x 17 3 x 3 4 450 x 440 x 86 5 BP72RT 86 4 39 2 23 8 x 17 3 x 3 4 605 x 440 x 8...

Страница 51: ...LV models 96 for 1K SUINT models 95 8 for 1 5K LV models 96 5 for 1 5K SUINT models 96 8 for 2K LV models 98 for 2K SUINT models 97 2 for 3K LV models 98 for 3K SUINT models 83 for 750 LV models 83 f...

Страница 52: ...Primary 2 5 15R Group 1 2 5 15R Group 2 No SU1000RTXLCD2U SU1000RTXLCD2UN SU1500RTXLCD2U SU1500RTXLCDN SU2200RTXLCD2U SU2200RTXLCDN 5 20R 2 L5 20R 1 Primary 5 20R 2 Group1 5 20R 2 Group2 No SU3000RTX...

Страница 53: ...losure IP rating IP20 Storage Temperatures 0 to 40 C 32 to 104 F with batteries 25 to 55 C 13 to 130 F without batteries Transit Temperature 25 to 55 C 13 to 130 F Relative Humidity 0 to 96 no condens...

Страница 54: ...614 2132501 614 21325 01...

Отзывы: