Instruction Leaflet 

IL 29C703D

Effective April 2011

Installation Instructions for Eaton Series C 600 Amp HLD-DC 

Circuit Breakers, Circuit Breaker Frame and Molded Case Switch 

EATON CORPORATION www.eaton.com

D

D

WARNING

THEDVOLTAGESDINDENERGIZEDDEQUIPMENTDCANDCAUSEDDEATHDORDSEVERED

PERSONALDINJURY.DBEFOREDMOUNTINGDTHEDCIRCUITDBREAKERDINDAND

ELECTRICALDSYSTEM,DMAKEDSUREDTHEREDISDNODVOLTAGEDPRESENTD

WHEREDWORKDISDTODBEDPERFORMED.D

otee:

N

Depending on the equipment configuration, the circuit breaker can be 

mounted using different styles of hardware . The following steps describe 

how to mount the circuit breaker using standard hardware . When special 

hardware is needed (for example, with the motor operator), the Instruction 

Leaflet describing the accessory also describes the special mounting arrange-

ments .

2-6 . To mount the circuit breaker, perform the following steps: 
a . 

For individual surface mounting, drill the mounting panel using 

the drilling plan shown in 

Figure 7

 . For panelboard mount-

ing, only load end support mounting holes are required . For 

Deadfront cover applications, cut out cover to correct escutch-

eon dimensions, see 

Figure 8

 . 

b . 

If the circuit breaker includes factory or field installed internal 

accessories, make sure accessory wire is accessible when 

the circuit breaker is mounted . 

otee:

N

Labels with accessory connection schematic diagrams are provided on 

the side of the circuit breaker .

c . 

Position the circuit breaker on the mounting surface . 

d . 

Install circuit breaker mounting screws and washers . Tighten 

screws firmly, but do not exceed 28 lb .-in . (3 N .m) .

Figure 7. 3-Pole Circuit Breaker Mounting Bolt Drilling Plans.

Figure 8. Circuit Breaker Escutcheon Cutout Dimensions for 

3-Pole Circuit Breakers.

D

D

CAUTION

WHENDALUMINUMDCONDUCTORSDAREDUSED,DTHEDAPPLICATIONDOFD

ADSUITABLEDJOINTDCOMPOUNDDISDRECOMMENDEDDTODREDUCEDTHED

POSSIBILITYDOFDTERMINALDOVERHEATING.DOVERHEATINGDCANDCAUSED

NUISANCEDTRIPPINGDANDDDAMAGEDTODTHEDCIRCUITDBREAKER.D

2-7 .  Connect line and load conductors and accessory leads . 
2-8 .  After the circuit breaker is installed, check all mounting hard-

ware and terminal connecting hardware for correct torque 

loading . Torque values for line/load terminals are given in  

Table 2

 and on the circuit breaker nameplate . 

2-9 .  Install both the line and load terminal covers on the circuit 

breaker cover with mounting screws provided . Torque to 

20-22 lb . in . (2 .26-2 .49 N .m) .

2-10 .  When step-type terminals (Cat . No . TA603LD) are used, ter-

minal shields (supplied with terminals) must be installed on 

the circuit breaker (

Figure 9

) and secured using retainer and 

screws included with the terminal shield kit .  Warning label 

supplied with the kit must be attached to the circuit breaker 

cover .

,

Line End

3-Pole

Circuit Breaker

1.719

(43.66)

I

Circuit

Breaker

Handle

-

-

0.250

(6.35)

I

Radius

1.500

(38.10)

7.281

(184.94)

Load End

3.438

(87.33)

0.188

(4.77)

Radius

3.641

(92.49)

2.292

(58.22)

1.325

(33.66)

3.281

(83.34)

Line End

0.250-20

Tap

(4

Holes)

Circuit

Breaker

Load End

Dimensions in Inches

(Millimeters)

(M6-1.0)

9.531

(242.09)

5.052

(128.32)

4.479

(113.77)

1.375

(34.93)

2.750

(69.85)

Circuit

Breaker

Handle

Содержание TA602LD

Страница 1: ...ation and Thermal Magnetic Trip Unit Adjustment 5 Inspection and Field Testing 6 Effective April 2011 Supersedes IL 29C703C Dated 07 1998 Instruction Leaflet IL 29C703D Installation Instructions for E...

Страница 2: ...gment but should not be considered to be all inclusive or covering every application or circumstance which may arise Contact Eaton for further information or instructions 1 Introduction and General In...

Страница 3: ...2 1 Compare nameplate data with existing equipment ratings and system requirements to make sure that the circuit breaker is suitable for the intended installation Prior to mounting confirm that the c...

Страница 4: ...on the mounting surface d Install circuit breaker mounting screws and washers Tighten screws firmly but do not exceed 28 lb in 3 N m Figure 7 3 Pole Circuit Breaker Mounting Bolt Drilling Plans Figur...

Страница 5: ...ustment Manual Operation The circuit breaker handle and the Push To Trip button in the trip unit control manual operation of the circuit breaker The circuit breaker handle has three positions two of w...

Страница 6: ...times to be sure that the mechanical linkages operate freely and do not bind If mechanical linkages do not operate freely replace cir cuit breaker 4 3 With the circuit breaker in the ON position pres...

Страница 7: ...uction Leaflet IL 29C703D Effective April 2011 Installation Instructions for Eaton Series C 600 Amp HLD DC Circuit Breakers Circuit Breaker Frame and Molded Case Switch EATON CORPORATION www eaton com...

Страница 8: ...sidered all inclusive If further information is required you should consult an authorized Eaton sales representative The sale of the product shown in this literature is subject to the terms and condit...

Отзывы: