Installation
10
Eaton T2235 Series eATS ePDUs P-164000014—Rev 1
www.eaton.com/ePDU
KIT-CABLRES-03 Universal Cable Restraint System
The following parts for installing the optional cable restraint tray are located in the KIT-CABLRES-03 shipping
carton:
l
(1) Cable management tray (001-2211-2)
l
(2) Mounting brackets (001-2233-2)
l
(11) 6-32 X 1/4” black screws (035-1606)
l
(12) Tie-wraps, 8” (010-0008)
Before You Install
Consider where you will locate the T2235 Series eATS ePDU model. These models are typically mounted at
the bottom or rear of the equipment cabinet. This location is convenient because heavy power cables are
usually routed at the bottom of the cabinet.
Ensure that you select a location with proper spacing. The T2235 Series eATS ePDUs typically require 44.5 mm
(1.75”) of vertical mounting space and extend 177.8 mm to 241.3 mm (7–9.5”) into the mounting rack of the
cabinet. Eaton recommends mounting the ePDU as close as possible to the equipment it controls.
Determine if you need additional weight support. The ePDU is designed to support its own weight only. Eaton
recommends using cable management and support brackets, such as the KIT-CABLRES-01 Universal Cable
Restraint System.
Consider temperature specifications in the installation site. Ambient temperature at the installation site should
not exceed 35°C (95°F). Relative humidity should remain below 95%, noncondensing.
CAUTION
The ePDU uses unpainted mounting brackets that serve as grounding to the rack. No separate
ground connection is necessary. For proper grounding, the electrical connection between the
T2235 Series eATS ePDU and the cabinet or rack must be secure.
Installing Optional Mounting Hardware
For T2235 Series eATS ePDU models, optional mounting hardware is available, including attachable cable
restraint trays.
Cable Restraint Tray
To install the cable restraint tray:
1.
Place the ePDU on a flat, stable surface.
2.
Slide the cable restraint tray onto the ePDU. Align the holes in the tray bracket with the screw holes on
the ePDU.
3.
Secure the cable restraint tray to the ePDU with the tray mounting screws (supplied).
4.
Secure the ePDU with attached cable restraint tray to the rack rails with the ePDU mounting screws
(supplied).
5.
This procedure is completed.
Содержание T2235 Series
Страница 1: ...Eaton T2235 Series Automatic Transfer Switch eATS ePDU Installation Operations and Maintenance Guide ...
Страница 5: ...Table of Contents ii Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Страница 9: ...Introduction 4 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Страница 13: ...Safety 8 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Страница 19: ...Installation 14 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Страница 23: ...Operation 18 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Страница 25: ...Maintenance 20 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Страница 35: ...Service 30 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Страница 39: ...Warranty 34 Eaton T2235 Series eATS ePDUs P 164000014 Rev 1 www eaton com ePDU ...
Страница 40: ... blank part number blank rev P 164000014 1 ...