SCHEMATIC

BLACK - 

HOT 120 

THROUGH 

277 VAC

WHITE - 

NEUTRAL

SELF-DIAGNOSTIC 

CHARGER/DRIVER PCB

TIME 

DELAY 

JUMPER

BATTERY

LED 

HEADS

BROWNOUT 

CIRCUIT 

VOLTAGE 

SELECTOR

YELLOW (-)

PURPLE (+)

LED REMOTE

HEADS

SCHEMATIC

D9

C1

J1

JP3

CN7

C3

+

C2

+

T1(EE19)

CN3

CN2

SW2

C6

C4

MOV1

CN1

J4

L1

CN4

J2

J3

PR1

SW1

LED1

CN5

F1

C5

JP1

JP2

F2

D1

L2

H+

H-

JP4

+

+

JP6

JP5

SPT-1

277VAC

240VAC

120VAC

RMT-

BATT

W

B

TDM

+

RMT+

Remote

1

4

5

8

C19

Installation Instructions for the Sure-Lites XR6C-LED Emergency Light.

Clearing Failure Code

• A battery failure (LED two blink red) can be cleared by replac-
ing the battery. Disconnecting the battery and AC power, or 
performing a full 90 minute discharge, will reset the error code, 
however, it will return if the battery is faulty.

• Charge Circuit (LED three blink red) and lamp/LED failure (LED 
four blink red) will clear when the unit successfully passes a 
manual or automatic 30 second test.

Indicators

• LED Off -No power to unit, emergency mode.

• LED Steady Green -Unit is fully charged and is float charging 
the battery to maintain readiness.

• LED Green Pulse - Unit is in a 24 hour fast charge of the bat-
tery..

• LED Two Blink Red -Battery has failed a capacity test, or the 
battery is disconnected. See “Clearing Failure Codes” above.

• LED Three Blink Red - Battery charge circuit has failed. See 
“Clearing Failure Codes” above.

• LED Four Blink Red - Lamps have burned out, or on an EXIT/
Combo, 50% or more of the LEDs have failed. See “Clearing 
Failure Codes” above.

• LED Steady Yellow - 30 second test or 10 second quick test 
(Fast Charge only).

• LED Blinking Yellow - 90 minute test.

MAINTENANCE

None required. Replace the batteries as needed according to 
ambient conditions. However, we recommend that the equip-
ment be tested regularly in accordance with local codes. 

NOTE:

 Servicing of any parts should be performed by qualified 

personnel. Only use replacement parts supplied by Eaton 
Lighting. 

CAUTION:

 This equipment is furnished with a sophisticated low 

voltage battery dropout circuit to protect the battery from over 
discharge after its useful output has been used. Allow 24 hours 
recharge time after installation or power failure for 90 minute 
testing. 

TROUBLE SHOOTING GUIDE 

If LED heads or charge indicator LED does not illuminate, check 
the following: 

1. Check AC supply – verify that unit has 24 hour AC supply. 

2. Unit is shorted or battery is not connected. 

3. Battery discharged. Permit unit to charge for 24 hours and 

then re-test. 

4. If following the above trouble shooting hints does not 

solve your problem, contact your local Eaton Lighting 
representative for assistance.

SURE-LITES

 

STEADY BLINK 

GREEN - FAST 

CHARGE

STEADY YELLOW - 

QUICK TEST

4 BLINK RED - LAMP / 

LED FAILURE

3 BLINK RED - CHARGE 

CIRCUIT FAILURE

STEADY BLINK YELLOW 

- 90 MINUTE TEST

STEADY GREEN - 

FULL / FLOAT 

CHARGE

2 BLINK RED - 

BATTERY FAILURE

OFF - EMERGENCY 

MODE / POWER OFF

Eagle Eye
Self-Diagnostics