Installation Instructions for the Sure-Lites SELM25R16SD/SELM50R14SD/SELM60R10SD Emergency Light
© 2017 Eaton
All Rights Reserved
Printed in USA
Impreso en los EE. UU.
Publication No. IB505061EN
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
Eaton es una marca commercial
registrada. Todas las marcas
comerciales son propiedad de sus
respectivos propietarios.
Warranties and Limitation of Liability
Please refer to
www.eaton.com/LightingWarrantyTerms
for our terms and conditions.
SCHEMATIC
BLACK -
HOT 120
THROUGH
277 VAC
WHITE -
NEUTRAL
SELF-DIAGNOSTIC
CHARGER/DRIVER PCB
TIME
DELAY
JUMPER
BATTERY
LED
HEADS
BROWNOUT
CIRCUIT
VOLTAGE
SELECTOR
YELLOW (-)
PURPLE (+)
LED REMOTE
HEADS
SCHEMATIC
D9
C1
J1
JP3
CN7
C3
+
C2
+
T1(EE19)
CN3
CN2
SW2
C6
C4
MOV1
CN1
J4
L1
CN4
J2
J3
PR1
SW1
LED1
CN5
F1
C5
JP1
JP2
F2
D1
L2
H+
H-
JP4
+
+
JP6
JP5
SPT-1
277VAC
240VAC
120VAC
RMT-
BATT
W
B
TDM
+
RMT+
Remote
1
4
5
8
C19
Installation Instructions for the Sure-Lites XR6C-LED Emergency Light.
Clearing Failure Code
• A battery failure (LED two blink red) can be cleared by replac-
ing the battery. Disconnecting the battery and AC power, or
performing a full 90 minute discharge, will reset the error code,
however, it will return if the battery is faulty.
• Charge Circuit (LED three blink red) and lamp/LED failure (LED
four blink red) will clear when the unit successfully passes a
manual or automatic 30 second test.
Indicators
• LED Off -No power to unit, emergency mode.
• LED Steady Green -Unit is fully charged and is float charging
the battery to maintain readiness.
• LED Green Pulse - Unit is in a 24 hour fast charge of the bat-
tery..
• LED Two Blink Red -Battery has failed a capacity test, or the
battery is disconnected. See “Clearing Failure Codes” above.
• LED Three Blink Red - Battery charge circuit has failed. See
“Clearing Failure Codes” above.
• LED Four Blink Red - Lamps have burned out, or on an EXIT/
Combo, 50% or more of the LEDs have failed. See “Clearing
Failure Codes” above.
• LED Steady Yellow - 30 second test or 10 second quick test
(Fast Charge only).
• LED Blinking Yellow - 90 minute test.
MAINTENANCE
None required. Replace the batteries as needed according to
ambient conditions. However, we recommend that the equip-
ment be tested regularly in accordance with local codes.
NOTE:
Servicing of any parts should be performed by qualified
personnel. Only use replacement parts supplied by Eaton
Lighting.
CAUTION:
This equipment is furnished with a sophisticated low
voltage battery dropout circuit to protect the battery from over
discharge after its useful output has been used. Allow 24 hours
recharge time after installation or power failure for 90 minute
testing.
TROUBLE SHOOTING GUIDE
If LED heads or charge indicator LED does not illuminate, check
the following:
1. Check AC supply – verify that unit has 24 hour AC supply.
2. Unit is shorted or battery is not connected.
3. Battery discharged. Permit unit to charge for 24 hours and
then re-test.
4. If following the above trouble shooting hints does not
solve your problem, contact your local Eaton Lighting
representative for assistance.
SURE-LITES
STEADY BLINK
GREEN - FAST
CHARGE
STEADY YELLOW -
QUICK TEST
4 BLINK RED - LAMP /
LED FAILURE
3 BLINK RED - CHARGE
CIRCUIT FAILURE
STEADY BLINK YELLOW
- 90 MINUTE TEST
STEADY GREEN -
FULL / FLOAT
CHARGE
2 BLINK RED -
BATTERY FAILURE
OFF - EMERGENCY
MODE / POWER OFF
Eagle Eye
Self-Diagnostics