SURE-LITES

 Installation Instructions for the Sure-Lites SELM25R16SD/SELM50R14SD/ 

SELM60R10SD Emergency Light

 WARNING 

Risk of Fire/Electric Shock

If not qualified, consult an electrician.

  WARNING 

Risk of Electric Shock

Disconnect power at fuse or circuit breaker before 

installing or servicing.

IMPORTANT SAFEGUARDS

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY 
PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING 
THE FOLLOWING.

READ AND FOLLOW ALL

SAFETY INSTRUCTIONS

 

1. Do not use outdoors. 

2. Do not use in hazardous locations, or near gas or electric 

heaters. 

3. Do not let power supply cords touch hot surfaces. 

4. Do not use this equipment for other than the intended use. 

5. Installation is to be performed only by qualified personnel. 

6.  Install in accordance with National Electric Code and local    

regulatory agency requirements. 

7.  The use of accessory equipment not recommended by the   

manufacturer may cause an unsafe condition. 

8. Equipment should be mounted in locations and at heights 

where it will not readily be subjected to tampering by 
unauthorized personnel. 

SAVE THESE

INSTRUCTIONS

MAX MOUNTING HEIGHT: 27.6 ft.

INSTALLATION

1.  De-energize the circuit at the junction box (J-box) where 

the emergency light is to be installed. 

2.  Open the emergency light by removing the sheet metal 

screw from the bottom of the fixture, then tipping the 
cover up off of the backplate (See Fig. 1).

3.  To mount to a junction box - Knock out the appropriate 

mounting pattern and the wire pass hole in the backplate 
to fit the J-box being used.

4.  To mount using conduit, mount the backplate to the wall 

in the desired location. Attach a conduit hub to whichever 
of the three conduit mount points on the backplate is most 
convenient. (see Fig. 2) Remove the corresponding U shaped 
cover from the housing by wiggling it back and forth until it 
breaks free. (see Fig. 3)

NOTE:

 A fourth conduit mount location is available on the 

bottom surface of the housing, but it can only be used with 
flex conduit. 

5.  Once the backplate is secured, the housing can be held in 

place during installation using the EZ Hang feature. (Fig. 2)

6. Connect incoming ground to the green ground wire.
7. Connect the incoming wires to the fixture’s power supply 

wires using the wire nuts provided.  Connect the white 
wire to neutral.  Connect the black wire to the hot lead.  
The SELM25R16SD / SELM50R14SD / SELM60R10SD uses 
a universal input power supply that will accept from 120-
277VAC (see Schematic).

8. Determine the incoming voltage, and select the appropriate 

jumper for the brownout circuit (see Schematic). Because of 
the universal input of the SELM25R16SD / SELM50R14SD / 
SELM60R10SD, the battery charger will continue to function 
if voltage sags, even if the normal power lights in the area 
fail.  Selecting the appropriate incoming voltage sets the 
voltage threshold for the brownout circuit, so that the 
emergency lights will come on if voltage sags.  The fixture 
ships with the circuit set to 120V.

9. LED remotes can be connected using the violet (+) and yellow 

(-) wires. See schematic.

10. Replace the housing onto the backplate.  Secure the 

backplate with the sheet metal screw.

11. Remove EZ Key to connect the battery. Battery will not 

charge with the EZ Key in place.

12.Energize AC supply. The test button should illuminate, and 

the LED heads will illuminate briefly when the test button is 
pushed.

13.Adjust remote heads (not included) as needed.
14.Allow 24 hours for batteries to charge.
15.If the fixture is to be powered down for an extended period 

after initial installation, replace the EZ Key. This will prevent 
the battery from discharging when AC power is removed. 
However, it will also prevent the battery from charging when 
AC power is restored, so it must be removed once the unit is 
ready for regular operation.