44
Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
88..33..11
K
Kiirrkk K
Keeyy IInntteerrlloocckkss
Figure 17. Kirk Key Interlocks for Bypass Mode
Source 1
Source 2
Bypass 1
Bypass 2
Isolation 1
Isolation 2
Isolation MCCBs or MCSWs are not interlocked.
Bypass MCCBs are interlocked with
Key 3
:
Only one bypass should be closed at a time (to
prevent cross-connecting both sides).
Source 1 MCCB and Bypass 2 MCCB/MCSW are
interlocked with
Key 1
:
If Source 1 MCCB is closed,
Bypass 2 MCCB/MCSW must be open.
If Source 1 is open, Bypass must be closed.
Source 2 MCCB and Bypass 1 MCCB are interlocked
with
Key 2
:
If Source 2 MCCB is closed,
Bypass 1 MCCB/MCSW must be open.
If Source 2 is open, Bypass 1 is closed.
Bypass Mode is entered by physically setting up the MCCBs and MCSWs to go to bypass. The STS has key-
interlocked bypass MCCBs/MCSWs allowing logic to be disconnected from power sources without interrupting
output load power (
). Engaging the bypass and returning from bypass to STS normal mode both
require the operator to manipulate Kirk Keys and MCCBs or MCSWs.
Содержание STS 2000A
Страница 1: ...p n 164001127 Revision 01 Installation and Operation Manual Eaton Static Transfer Switch 2000A 3 Pole...
Страница 8: ......
Страница 16: ...xvi Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 List of Tables...
Страница 32: ...16 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Safety...
Страница 98: ...82 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Troubleshooting...
Страница 120: ...16400112701 164001127 01...