Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
35
C
Chhaapptteerr 77 O
Oppeerraattiioonnaall IInntteerrffaacceess
There are two STS operator interfaces:
•
The touchscreen display, which is the normal operator interface
•
The Redundant Operator Interface (ROI), which sets the operational mode and backs up the touchscreen
display
77..11
TToouucchhssccrreeeenn D
Diissppllaayy
The STS has a 10.4-inch diagonal touchscreen display. The STS has a comprehensive set of screens covering
setup, transfer controls, alarms, events, status, and measurements.
Changes to controls or parameters must be made from the touchscreen display; they cannot be changed
remotely from a Building Management System (BMS) or from a web browser. (The BMS can issue dry contact
control signals, such as Remote EPO or Remote Source Select.)
77..11..11
V
Vooiiccee U
Unniitt
A Voice Unit provides short audible statements that supplement text or graphics in certain situations, such as
“Static Switch, new alarm,” or “Static Switch, alarm cleared.” The Voice Unit also steps operator through text
procedures from the Help screens.
77..11..22
H
Hoom
mee S
Sccrreeeenn
The
Home
screen (
) is the first screen displayed when the STS is turned on.
Home
screen has a dynamic graphic 1-line mimic showing active and inactive paths from sources to output
with power measurements:
•
The active path between one source and the output is shown in yellow.
•
Inactive paths or bypass paths are shown in blue.
The
Status
Panel summarizes the general status of the unit. It shows which source is open or available, which
bypass is being used, and how many alarms are present.
The
Normal/Alarm
status indicator shows if alarms are present:
•
If no alarms are outstanding, the indicator is green and reads
Normal
•
If the indicator is red and reads
Alarm
, then the operator should touch the Alarms button on the bottom
row to access the
Alarms
screen for a list of outstanding alarms.
Transfers
panel has a counter of the number of transfers that have occurred since the last
Clear
of this
counter.
The
Home
screen also has
Preferred Source
control (see
Содержание STS 2000A
Страница 1: ...p n 164001127 Revision 01 Installation and Operation Manual Eaton Static Transfer Switch 2000A 3 Pole...
Страница 8: ......
Страница 16: ...xvi Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 List of Tables...
Страница 32: ...16 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Safety...
Страница 98: ...82 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Troubleshooting...
Страница 120: ...16400112701 164001127 01...