Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
31
Figure 12. Enhanced Contractor Board (Enhanced Remote Customer Interface Board)
66..11..22
EEnnhhaanncceedd C
Coonnttrraaccttoorr B
Booaarrdd C
Coonnnneeccttiioonnss
The Enhanced Contractor Board is available as an option. This expanded version allows for additional
connection points of previously discussed interfaces as well as additional high end interface options (
NOTE
Remote relays can accept dry contacts rated up to 2A/250V.
The Contractor Boards have multiple applications in Eaton PDI products and not all connections are supported
on the STS 2000A. The following connections are not currently supported on this product:
•
Inter-Range Instrumentation Group (IRIG) time codes
•
Cell-phone modem connection
66..11..33
M
Mooddbbuuss R
RTTU
U C
Coonnnneeccttiioonn
The STS has an isolated RS422/RS485 Modbus RTU interface with soft bias provided. Both Contractor Boards
have external connections for RS422/RS485. The Modbus interface can be configured for baud rate, parity, and
address on the
Settings
screen (See
). The address range is 1 to 255 and the address of
each device must be unique. Jumpers on the monitor circuit board select either a 2-wire or 4-wire
configurations for connection.
Содержание STS 2000A
Страница 1: ...p n 164001127 Revision 01 Installation and Operation Manual Eaton Static Transfer Switch 2000A 3 Pole...
Страница 8: ......
Страница 16: ...xvi Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 List of Tables...
Страница 32: ...16 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Safety...
Страница 98: ...82 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Troubleshooting...
Страница 120: ...16400112701 164001127 01...