Eaton SPD Series for Mounting External

to Electrical Distribution Equipment

1.5  Equipment Testing

WARNING

CONDUCTING DIELECTRIC, MEGGER, OR HI-POTENTIAL TESTING 

WITH THE SPD INSTALLED WILL CAUSE INTERNAL DAMAGE TO THE 

SPD. THE SPD WILL ALSO CAUSE THE TEST TO FAIL. 

Every Eaton SPD Series unit is tested at the factory for dielec-

tric breakdown. No further SPD testing is required for installa-

tion.
If you desire to test distribution equipment by performing 

dielectric, megger, or hi-potential tests, any installed SPD 

must

 

be disconnected from the power distribution system to prevent 

damage to the unit. 
Follow this procedure to safely disconnect the SPD:

1.  For SPDs connected to a circuit breaker or fuse:

a.  3-wire delta SPDs: Turn off the circuit breaker or remove 

the fuses from the fuse holder to isolate the SPD. 

b.  Wye and Split phase SPDs: Turn off the circuit breaker or 

remove the fuses from the fuse holder to isolate the SPD 

and remove the Neutral connection on Wye connected 

SPDs.     

2.0 Installation

WARNING

INSTALLING AN SPD THAT IS IMPROPERLY RATED FOR THE ELECTRI-

CAL SYSTEM VOLTAGE COULD CREATE A POTENTIALLY HAZARDOUS 

CONDITION, RESULTING IN INJURY OR EQUIPMENT DAMAGE. 

2.1 Preparation for Installation

CAUTION

EATON SPD SERIES PRODUCTS MUST BE INSTALLED OR  REPLACED 

BY A QUALIFIED ELECTRICIAN TO AVOID INJURY OR EQUIPMENT 

DAMAGE. 

Before installing an Eaton SPD Series unit, do the following:    

• 

Verify that the area is clear of any dirt, debris or clutter that 

may hamper the installation process. 

• 

Verify that there is enough space to install the SPD. See 

Section 2.3, "Installation Procedures" for dimensions. 

• 

Confirm that all tools and equipment needed for the installa-

tion are available. 

• 

Confirm that the system voltage and wiring configuration is 

the same as the SPD you are installing. Check the voltage 

rating label on the side of the SPD. 

WARNING

TURN OFF THE POWER SUPPLY BEFORE WORKING IN ANY ELECTRI-

CAL CABINET OR ON ANY CIRCUIT BREAKER PANEL. FAILURE TO DO 

SO COULD RESULT IN INJURY OR DEATH FROM ELECTRICAL SHOCK. 

NOTICE

A POOR GROUND, OR GROUNDING/BONDING VIOLATIONS, COULD 

PREVENT THE SPD FROM PERFORMING AS SPECIFIED. 

DO NOT USE THE SPD TO CARRY OR PASS THROUGH GROUND TO 

OTHER DEVICES OR LEADS. DAMAGE TO THE EQUIPMENT MAY 

RESULT. 

• 

Check the facility grounding system. All grounding, bonding, 

and earthing must meet the NEC and any other national, state 

and local electrical codes. 

2.2 Installation Locations

Eaton's SPD Series can be installed next to, above, or below any 

existing electrical enclosure.   
The ideal mounting location for the Eaton SPD Series is as close 

as possible to the electrical enclosure. The Eaton SPD Series 

should be mounted in such a way as to minimize any sharp 

bends in the wiring conduit.  

2.3 Installation Procedures

1.  Before mounting the SPD first determine the ideal location 

and ensure that the mounting surface is sufficient to sup-

port the weight of the SPD (See Figures 2, 3, 4, 5, and 6 on 

pages 4, 5, and 6 for model weights). The SPD should be 

mounted as close a possible to the electrical enclosure and 

as close as possible to the wiring connection point within the 

enclosure. This will ensure a minimum wire length and maxi-

mum SPD performance. 

2. Lay out the four enclosure mounting holes using the enclo-

sure dimensions provided in Figures 2, 3, 4, 5 and 6 on 

pages 4, 5 and 6. Drill the appropriate holes per the product 

dimensions. Note: NEMA 1 enclosures require a #10 fastener 

and NEMA 4 and 4X enclosures require a 1/4 inch fastener.

3. Determine the correct length and install metal conduit onto 

the SPD. NEMA 1 SPDs have a 3/4 inch trade size chase nip-

ple and NEMA 4 and NEMA 4X SPDs have 3/4 inch trade size 

hubs. Route all Phase, Neutral (where applicable), Ground 

and Form C (where applicable) wires through the conduit.

4. Determine the hole location on the receiving electrical enclo-

sure and either remove the knock-out provided or drill the 

appropriate size hole at this location. Route the SPD wires 

through the enclosure hole and mount the SPD enclosure.

5. Select the correct wiring diagram for the SPD you are install-

ing. You must refer to this diagram while wiring the SPD. See 

Figures 9 - 14.  SPD Series Type 1 and Type 2 units do not 

require over current protection devices, fuses or circuit break-

ers to operate correctly.  All local and national electric codes 

must be followed during installation and these codes may 

require protection of the conductors leading to the SPD unit.

6. Determine the wire length required to make the SPD Phase 

connections and cut the wires to the appropriate length. (To 

maximize SPD performance, wire length should be as short 

as possible). Connect the Phase wires. 

otee:

N

For wire lengths longer than 4 inches, Phase wires should 

be twisted once for each 4 inches of wire length to maximize SPD 

performance.

Содержание SPD050208Y1K

Страница 1: ...Distribution Equipment Instruction Manual IM01005031E Effective November 2012 Rev 2 Table of Contents 1 0 Introduction 2 0 Installation 3 0 Operating Features 4 0 Troubleshooting 5 0 Specifications 6...

Страница 2: ...nd are intended to be installed in applications with a degree of protection rated IP 20 1 3 Safety Precautions A licensed qualified electrician must complete all instructions in this manual in accorda...

Страница 3: ...eck the facility grounding system All grounding bonding and earthing must meet the NEC and any other national state and local electrical codes 2 2 Installation Locations Eaton s SPD Series can be inst...

Страница 4: ...tate and local electrical codes when mak ing these connections Figure 2 NEMA 1 With Flushmount Suffix L 4 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical...

Страница 5: ...K Figure 4 NEMA 4 4X Suffix N P 5 IM01005031E Rev 2 Effective November 2012 Eaton SPD Series For Mounting ExternalTo Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 Suffix K...

Страница 6: ...v 2 Effective November 2012 Eaton SPD Series For Mounting External To Electrical Distribution Equipment eaton corporation www eaton com NEMA 1 With Disconnect Suffix M Figure 5 NEMA 4 4X With Disconne...

Страница 7: ...al IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 7 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Figure 7 Flush Mount Plate For 50 200 kA Units In A NEMA 1...

Страница 8: ...on Equipment Instruction Manual IM01005031E Rev 6 BLUE WHITE RED WHITE ORANGE WHITE COMMON NORMALLY OPEN NORMALLY CLOSED Figure 8 Sidemount Form C Wires Figure 9 Split Phase Units Figure 10 3 Phase De...

Страница 9: ...t for each feature package Each display has both green and red light emitting diodes LEDs to indicate the status of the protection on each phase Green indicates the phase is fully protected Red indica...

Страница 10: ...the display 3 Remove the two phillips head screws that hold the display 4 Rotate the display to the desired position Be careful not to overstress the display ribbon cable 5 Place the display back onto...

Страница 11: ...Significant surge event Replace SPD Replace SPD with correct voltage model Check electrical system for TOV sources correct replace SPD Replace SPD One of the display Red LEDs is ON Audible Alarm is O...

Страница 12: ...nd 480D Basic voltage codes 600Y and 600D voltage codes 0 6W 1 7W 2 1W Protection modes Single split phase L N L G N G L L Single phase L N L G N G Three phase delta L G L L Three phase Wye L N L G N...

Страница 13: ...te Protection Status of the N G Mode on units with a Neutral Wire Audible alarm with Silence button Form C Relay Contact EMI RFI filtering Providing up to 50dB of Noise Attenuation from 10kHz to 100Mh...

Страница 14: ...thin said term determined by Eaton to be defec tive The giving of or failure to give any advice or recommenda tions by Eaton shall not constitute any warranty by or impose any liability upon Eaton The...

Страница 15: ...Instruction Manual IM01005031E Rev 6 Effective January 2019 Eaton www eaton com 15 Eaton SPD Series for Mounting External to Electrical Distribution Equipment Notes...

Страница 16: ...nd conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLU...

Отзывы: