Instruction Bulletin 

    

Instructions for Installation,

 

Page 5

 

Effective: July 2016 

Operation and Maintenance of the 

 

 

SL800 Classic 7.2 Kilovolt, 720 Amp. Vacuum Contactor 

For more information visit: 

www.eaton.com

 

IB48082 

 

 

 

 

Fig. 3  Coil Control Board with Dip Switch 

 

 

 

 
 

TABLE IIIb.  CONTROL BOARD DROPOUT SETTINGS 

Delay Setting 

SW4 

SW5 

SW6 

50 ms 

On 

Off 

Off 

130 ms 

Off 

On 

Off 

250 ms 

On 

On 

Off 

330 ms 

Off 

Off 

On 

 
The control board provides the economizing function 
for the main coil circuit.  The L63 interlock used in 
the economizing circuit on the SJA800A contactor is 
therefore not needed in this design.  It has been 
removed from the SL800 Classic contactor.   
 

WIRING

 

 
Refer to Figure 4 for standard control wiring for 
magnetically held contactors.  To close the contactor, 
apply power to terminals 1 and 2 on the control 

board.  Power must be maintained to terminals 1 and 
2 to keep the contactor in the closed position.  The 
closing coil is connected to terminals 5 and 6.  

 

 

Fig. 4  Connections for Magnetically Held Contactor 

 

 

RENEWAL AND REPLACEMENT PARTS 

 

 

SL800 Classic VI Assemblies, set of three -     

                                              54A1307G27 

 

 

Control Board   

         - 54A1307G24 

 

Contactor Coil                        - 54A1307G18 

 

Содержание SL800 Classic

Страница 1: ...attempting any installation operation or maintenance of the SL vacuum contactor Retain this document for future use This equipment shall be installed and serviced only by qualified electrical personnel A qualified person is one who is familiar with the construction and operation of this equipment and who is aware of the hazards involved Instructions for Installation Operation and Maintenance of th...

Страница 2: ... 6000 5000 4500 50 350 000 6200 7200 8000 10000 8000 6000 50 570 000 TABLE II RATINGS Maximum Interrupting Current 3 Operations 12 500A Control Voltages AC 110 120 220 240 Volts Rated Current 720 Amperes 50 60 Hz Maximum Rated Voltage 7 200 Volts DC 125 Volts Making Breaking Capacity Control Circuit Burden Rated Volt AC4 Make 8 000 Amperes UL 7 650 Amperes IEC Closing 2600 VA AC4 Break 6 400 Amper...

Страница 3: ...arter 4 Disconnect the control plug and stow it so that the cable will not be damaged Disconnect the two 3 point separable terminal blocks on the right front of the isolating switch 5 Trip the latch on the left side by holding it upward using your foot if desired when unit is at floor level 6 While holding the latch up pull the contactor out ward It will roll forward and should re latch at a deten...

Страница 4: ...1 and 2 The control board rectifies the input voltage and applies a pulse width modulated DC output voltage to the coil The output voltage is approximately full voltage for the first 200 milliseconds after energization during which time the contactor closes and seals The output voltage is then automatically reduced to approximately 15 VDC to maintain the contactor in the closed position The coil c...

Страница 5: ...circuit The L63 interlock used in the economizing circuit on the SJA800A contactor is therefore not needed in this design It has been removed from the SL800 Classic contactor WIRING Refer to Figure 4 for standard control wiring for magnetically held contactors To close the contactor apply power to terminals 1 and 2 on the control board Power must be maintained to terminals 1 and 2 to keep the cont...

Отзывы: