Installation
S811+ Soft Starter
MN03900001E—November 2012
7
Installation
Mounting
The S811+ does not require any special tools for mounting operations.
To aid with panel layout, refer to the dimension drawings on
Pages 8
–
10
. Drill holes per
mounting hole location as shown. Mounting hardware may utilize either tapped holes in the
panel or lock washers and nuts to secure the soft starter.
To mount the unit, use all the hardware specified in the table below.
Required Mounting Hardware
Note:
See
Page 3
for Weight Support Requirements.
Frame Size
Bolt Dia.
Length—
Minimum
Grade
Quantity—
Minimum
Torque—
Lb-in (Nm)
S811+N…
#10-32
0.5
5
4
15 (1.7)
S811+R…
1/4 in
0.625
5
4
25 (2.8)
S811+T…
1/4 in
0.625
5
6
30 (3.4)
S811+U…
1/4 in
0.625
5
6
30 (3.4)
S811+V…
1/4 in
1.50
8
8
50 (5.6)