![Eaton S611 Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/eaton/s611/s611_installation-leaflet_4104348003.webp)
3
Installation Leaflet
IL04209006E
Effective July 2010
PROFIBUS Module for use with
Motor Insight, C440 and S611
EATON CORPORATION
www.eaton.com
Approvals / Certifications
Electrical / EMC
ESD Immunity
+/- 8kV air, +/- 4kV contact
Radiated Immunity (IEC61000-4-3)
10V/m 80-1000 MHz, 80%
amplitude modulation @
1kHz
Fast Transient (IEC61000-4-4)
+/- 2kV communications
Surge (IEC61000-4-5)
+/- 2kV shield-to-ground
RF Conducted (IEC610000-4-6)
10V, 0.15 – 80MHz
Ingress Protection Code
IP20
Radiated and Conducted Emissions EN55011 (CISPR 11) Class A
Agency Certifications
UL
®
508
cUL
®
(CSA C22.2 No. 14)
CE (Low Voltage Directive)
PROFIBUS Certification
Module Electrical Requirements
Voltage Range
18 - 30 Vdc
Current Draw
Approx. 30 mA
Notes
For use with Eaton UL Listed Power Supply Catalog Nos. PSS55A,
PSS55B, PSS55C, or PS160E.
Any UL Listed isolated power supply with a maximum of 30 Vdc
output may be used, provided that a UL Listed or Recognized Fuse
rated no more than 3A maximum be installed.
5pin 24 VDC Power, RS485 Connector